Circuit breakers

FAZ-T xEffect Miniature Circuit Breaker

The FAZ-T miniature circuit breaker is a protective device equipped with both a thermal and an electromagnetic release that is available in 1-, 2-, 3-, 4-, 1+N and 3+N pole versions. The FAZ-T is available with rated currents of 1 A to 40 A. Depending on the device type, the switching capacity is 15 kA or 10 kA according to IEC/EN 60898-1, and 25 kA, 20 kA or 15 kA according to IEC 60947-2.

IN ACCORDANCE WITH
IEC/EN 60947-2 and IEC/EN 60898-1
VERSIONS
1-, 2-, 3-, 4-, 1+N and 3+N pole
TRIPPING CHARACTERISTICS
B, C and D

Core features

  • Premium miniature circuit breaker for industrial applications and building installations
  • Current limiting class 3
  • Back-up fuse with high selectivity, thanks to low let-through energy
  • Contact position indicator red – green
  • Rated currents up to 40 A
  • Tripping characteristics B, C and D
  • Rated switching capacity 15 kA or 10 kA according to IEC/EN 60898-1, and 25 kA, 20 kA or 15 kA according to IEC/EN 60947-2
  • Compatible with standard busbars
  • Comprehensive range of accessories, which can also be retrofitted

Reliable cable protection

MCBs protect cables against damage due to overload and short circuits: In the event of dangerously high currents, the circuit breaker’s bimetallic thermal release will disconnect the power supply. In the event of a short circuit, the electromagnetic release will disconnect the power supply in a timely manner.

A design that is standard-compliant and quality-tested

Part 1 of IEC/EN 60898 applies to AC MCBs if the rated voltage between the phases does not exceed 440 V, the rated current does not exceed 125 A and the rated breaking capacity does not exceed 25,000 A. Circuit breakers that fall within the scope of IEC/EN 60898-1 are designed to be operated by non-experts. IEC/EN 60947-2 (VDE 0660-101) applies to circuit breakers in circuits with rated voltages up to 1,000 V AC, or up to 1,500 V DC.

The right MCB for every situation

Circuit breakers with tripping characteristic B are the standard MCB type used for lighting and socket outlet circuits. For circuits with high inrush and peak currents (e.g. motors and luminaire banks) devices with tripping characteristic C are used. Circuit breakers with tripping characteristic D are used for circuits with inductive and capacitive loads (solenoid valves, transformers etc.).

Maximum safety in railway applications

The xEffect range of protective switchgear also ensures highest standards of safety in railway applications. Thanks to compliance with specific standards such as IEC 61373 (Rolling stock equipment – Shock and vibration) and EN 45545-2 (fire protection of railway vehicles), the devices provide maximum safety and performance in rolling stock applications. In addition to standard switchgear, we also offer a wide range of MCBs and RCDs for the connection of ring cable lugs in railway applications.