Adaptive Evacuation Control Unit for wall mounting with integrated battery-supported power supply or for assembly in ZB-S/18-AE units using loop technique for controlling addressable adaptive exit sign luminaires with 230V / 216V AC/DC technology for safety lighting systems acc. to DIN VDE 0100-560, DIN EN 50172 and V DIN V VDE 0108-100.
With automatic testing device and monitoring of loop bus communication and individual display of condition and name of loop BUS connection per GuideLed DXC luminaire.
Building upon decades of expertise in the delivery of life safety systems, and particularly emergency lighting technologies, Eaton’s Adaptive Evacuation System enables faster, safer and more agile evacuations, particularly when deployed alongside a public address/voice alarm solution that provides additional guidance.
When installed, the system is programmed with a range of potential exit routes. Based on information from CCTV, fire detection and other devices that pinpoint the nature and location of a hazard, it can select the safest and fastest route for occupants and an appointed system operator within the building is given the opportunity to accept or reject this recommendation, so that occupants can be directed accordingly.
Unlike ‘active’ and ‘dynamic’ systems, Eaton’s technology is fully adaptable and its instructions can be modified in real-time. It has been extensively tested and conforms with current regulatory requirements, although the technology is so new that standards are still to be fully defined.
Exit sign luminaires designate the escape route out of the building always in the same direction, independently of a dangerous situation.
Exit sign luminaires block unsafe escape routes in evacuation situations, thereby guiding those fleeing out of the building via the safe escape routes.
Exit sign luminaires block unsafe escape routes and release these as soon as they become safe again. This enables dynamic hazard situations (e.g in case of fire or attacks) to be flexibly responded to.
The GuideLed DXC LED exit sign luminaire is in keeping with German / European standards EN 60598-1, DIN EN 60598-2-22, DIN 4844-1 and DIN EN 1838 with additional function for displaying a red ‘X’ to signify an area as closed or blocked.
Special LED converter with integrated monitoring module for single luminaire monitoring with 20-digit address switches and integrated bus interface for direct connection to Eaton’s Adaptive Evacuation system with the use of the EATON AE-CU via a dataline.
Order code | Description |
40071361359 | AE-CU-W, Surface- / Recessed mounted wall housing |
Primary rated voltage | 230 V AC +10%, -15% |
Primary rated current | 75 mA |
Nominal frequency | 50 Hz |
Protection rating | IP 30 |
Insulation class | I |
Ambient temperature | -5°C to+40°C |
Secondary rated voltage | 18,5 V - 29,5 V |
Battery | 2 x 12 V / 12 Ah |
Max. battery current | 3.5 A |
Charge characteristic | Constant voltage temperature-compensated |
Min. backup power time | 30 h |
Weight with battery | 14 kg |
Dimensions (HxWxD in mm) | 395 x 495 x 180 |
Basic housing material | Sheet steel, powder-coated |
Material of front | Plastic |
Inputs | |
Addressable loop line | 4 |
Scenario active inputs | 2 (more on request) |
Maximum ring length | 2,000 m / I(ST)Y 4 x 2 x 0.8 mm |
Maximum number of GuideLed DX/DXC luminaires per loop | 60 |
Outputs | |
Zero-potential changeover contact | 2 |
Contact load | 24 V / 1 A |
Fuse | 1.35 A |
Order code | Description |
40071361360 | *AE-CU-E, Installation variant for ZB-S/18-AE |
*note: not suitable for AT-S+ and LP-STAR systems |
Primary rated voltage | 28.5 V/DC |
Primary rated current | 4.2 A |
Protection rating | IP 20 |
Insulation class | I |
Ambient temperature | -5°C to+40°C |
Secondary rated voltage | 18.5 V - 29.6 V |
Weight | 8 kg |
Dimensions (HxWxD in mm) | 200 x 500 x 190 |
Material | Sheet steel, powder-coated |
Inputs | |
Addressable loop line | 4 |
Scenario active inputs | 2 (more on request) |
Maximum ring length | 2,000 m / I(ST)Y 4 x 2 x 0.8 mm |
Maximum number of GuideLed DX/DXC luminaires per loop | 60 |
Outputs | |
Zero-potential changeover contact | 2 |
Contact load | 24 V / 1 A |
Fuse | 1.35 A |