LED Supply and Monitoring module for a LED series connection (1-8 LEDs, 350mA, 1-5 LEDs, 500mA, 1-3 LEDs, 700mA, 1-2 LEDs, 1000mA) with integrated monitoring module for single luminaire monitoring (without additional data line) and 20 addresses for function monitoring (CEWA GUARD Technology).
Three types of LED supply- and monitoring modules are available. The SLS types are suitable for typical standard applications. The SLR types are specially designed for installation in flush-mounted switch boxes. The SLI types meet higher requirements such as supply of up to 8 LEDs, wider temperature range and incl. single LED monitoring.
Switching modes (maintained/non-maintained and switched emergency luminaires) are freely programmable in one circuit without an additional data line to the luminaires in conjunction with suitable emergency lighting systems (with STAR-Technology).
Error message in case of: Interruption in the LED series connection or a short circuit at the output terminals. Safe fault identification even if one LED fails due to Single individual monitoring (SLI technology = Single LED monitoring Intelligence). Extended ambient temperature area from -40°C to +50°C.
The new SLI technology (Single LED monitoring Intelligence) enables a safe error message even if a single LED fails. Up to 8 LEDs in series connection can thus be individually monitored.
Combined with an automatic function test, this signals a reduced luminaire luminous flux emission due to a defective LED and necessary repair work can be initiated immediately by the operating personnel.
Maintaining building security by complying with the required lighting parameters for safety lighting is significantly improved by this procedure.
The LED drivers range is suitable for operation in cold ambient conditions down to -40°C such as cold storage facilities.
In addition, the new SLI LED power supply modules can be used under extreme temperature conditions in the range of - 40° C to + 50° C. The possible applications of these new power supply modules thus cover a huge applications.
The ENEC symbol (European Norms Electrical Certification) is a European examination symbol created by CENELEC (European Committee for Electrical Standardisation) which confirms that the device on which this symbol is fixed to automatically complies with all requirements of the European testing laboratory.
All Eaton modules must be subjected to these stringent tests and are then allowed to display this symbol.
With Eaton monitoring modules, electronic ballasts or LED supply modules, luminaires for general lighting systems from any manufacturer can be connected to central battery systems and thus integrated into the building emergency lighting concept.
The modules matched to the requirements of central battery systems installations make it possible to monitor and control up to 20 luminaires in only one circuit.
Using the ballasts, luminaires on one circuit can be operated in different switching modes such as maintained light, non-maintained light or switched maintained light. Here in the case of the N-EVGs (electronic ballasts), the emergency lighting level of each lamp can be individually set for battery operation from 30 to 100 % of the nominal luminous flux.
Your search "" did not match any documents or products.
Without individual packaging Order Code |
Individual packaging Order Code |
Description |
40071349560 | 40071355260 | V-CG-SLI 350 |
40071349561 | 40071355261 | V-CG-SLI 500 |
40071349562 | 40071355262 | V-CG-SLI 700 |
40071349563 | 40071355263 | V-CG-SLI 1000 |
40071352419 | 40071352449 | V-CG-SLS 28 |
40071352417 | 40071352447 | V-CG-SLS 350 |
40071352418 | 40071352448 | V-CG-SLS 500 |
40071352369 | 40071355264 | V-CG-SLS 501 |
40071352399 | 40071355265 | V-CG-SLS 701 |
40071352420 | 40071352450 | V-CG-SLR 350 |
40071352421 | 40071352451 | V-CG-SLR 28 |
40071351928 | Module housing with stain relief |
Technical data | V-CG-SLI 350 | V-CG-SLI 500 | V-CG-SLI 700 | V-CG-SLI 1000 |
Primary side (data valid for full load) | ||||
Rated voltage ranges | 220 - 240 V, 50/60 Hz / 176 - 275 V DC | 220 - 240 V, 50/60 Hz / 176 - 275 V DC | 220 - 240 V, 50/60 Hz / 176 - 275 V DC | 220 - 240 V, 50/60 Hz / 176 - 275 V DC |
Standby power loss | < 0.5 W (230 V / 50 Hz) | < 0.5 W (230 V / 50 Hz) | < 0.5 W (230 V / 50 Hz) | < 0.5 W (230 V / 50 Hz) |
Current consumption 220 V DC | 43 mA | 43 mA | 43 mA | 38 mA |
Power input | 11.6 VA / 10.7 W | 11,5 VA / 11,3 W | 10.9 VA / 9.5 W | 9.5 VA / 7.8 W |
Power factor | 0.9 | 0.9 | 0.88 | 0.8 |
Inrush current | ≤ 3.0 A | ≤ 3.0 A | ≤ 3.0 A | ≤ 3.0 A |
Operating frequency | 30 kHz - 450 kHz | 30 kHz - 450 kHz | 30 kHz - 450 kHz | 30 kHz - 450 kHz |
Connection terminals | Clamp terminals 2.5 mm² / reverse-polarity protected | Clamp terminals 2.5 mm² / reverse-polarity protected | Clamp terminals 2.5 mm² / reverse-polarity protected | Clamp terminals 2.5 mm² / reverse-polarity protected |
Secondary side | ||||
Output current | 350 mA +/- 10% | 500 mA +/- 10% | 700 mA +/- 10% | 1000 mA (1 LED) / 880 mA (2 LEDs) +/- 10% |
Output voltage | 30 V DC (open-circuit operation) +/- 10% | 30 V DC (open-circuit operation) +/- 10% | 30 V DC (open-circuit operation) +/- 10% | 30 V DC (open-circuit operation) +/- 10% |
Output voltage in operation | 25 V +/- 10% (8 LEDs) | 16,5 V +/- 10% (5 LEDs) | 11.0 V +/- 10% (3 LEDs) | 8 V +/- 10% (2 LEDs) |
Lamp load | 1-8 LEDs (rated current 350 mA), series connection (UF = 2.85 ... 3.12 V) | 1-5 LEDs (rated current 500 mA), series connection (UF = 2.85 ... 3.3 V) | 1-3 LEDs (rated current 700 mA), series connection (UF = 2.85 ... 3.67 V) | 1-2 LEDs (rated current 1000 mA), series connection (UF = 2.85 ... 4.0 V) |
Output power (max.) | 8.75 W | 8.5 W | 8.05 W | 7.04 W |
Connection terminals | 1.5 mm² / not reverse-polarity protected | 1.5 mm² / not reverse-polarity protected | 1.5 mm² / not reverse-polarity protected | 1.5 mm² / not reverse-polarity protected |
Maximum line length | 0.5 m (module – LED) | 0.5 m (module – LED) | 0.5 m (module – LED) | 0.5 m (module – LED) |
Type of mounting | To be mounted in luminaires with protection category I or II | To be mounted in luminaires with protection category I or II | To be mounted in luminaires with protection category I or II | To be mounted in luminaires with protection category I or II |
Degree of protection | IP20 | IP20 | IP20 | IP20 |
Permissible ambient temperature | ta = –40 °C to +50 °C | ta = –40 °C to +50 °C | ta = –40 °C to +50 °C | ta = –40 °C to +50 °C |
Maximal permissible test point temperature | tc = 70 °C | tc = 70 °C | tc = 70 °C | tc = 70 °C |
Dimensions in mm (L x H x W) | 110 x 30 x 21 | 110 x 30 x 21 | 110 x 30 x 21 | 110 x 30 x 21 |
Housing material / Colour | Flame retardant polycarbonate / grey | Flame retardant polycarbonate / grey | Flame retardant polycarbonate / grey | Flame retardant polycarbonate / grey |
Weight | 0.042 kg | 0.042 kg | 0.042 kg | 0.042 kg |
Luminous flux ΦE/ΦN at the end of rated operating time (EBLF) | 100% | 100% | 100% | 100% |
Technical data | V-CG-SLS 350 | V-CG-SLS 500 | V-CG-SLS 501 | V-CG-SLS 701 |
Primary side (data valid for full load) | ||||
Rated voltage ranges | 220 - 240 V, 50/60 Hz / 176 - 275 V DC | 220 - 240 V, 50/60 Hz / 176 - 275 V DC | 220 - 240 V, 50/60 Hz / 176 - 275 V DC | 220 - 240 V, 50/60 Hz / 176 - 275 V DC |
Standby power loss | < 0.5 W (230 V / 50 Hz) | < 0.5 W (230 V / 50 Hz) | < 0.5 W (230 V / 50 Hz) | < 0.5 W (230 V / 50 Hz) |
Current consumption 220 V DC | 41 mA (230 V AC) / 26 mA (220 V DC) | 36 mA (230 V AC) / 21 mA (220 V DC) | 24 mA (230 V AC) / 15 mA (220 V DC) | 33 mA (230 V AC) / 21 mA (220 V DC) |
Power input | 9.4 VA (230 V AC) | 8.2 VA (230 V AC) | 6.0 VA (230 V AC) | 7.3 VA (230 V AC) |
Power factor | 0.60...0.70 | 0.55 | 0.57 | 0.59 |
Inrush current | ≤ 1.5 A | ≤ 1.5 A | ≤ 1.5 A | ≤ 1.5 A |
Operating frequency | 132 kHz | 132 kHz | 132 kHz | 132 kHz |
EEI | A2 | A2 | A2 | A2 |
Connection terminals | Clamp terminals 2.5 mm² / reverse-polarity protected | Clamp terminals 2.5 mm² / reverse-polarity protected | Clamp terminals 2.5 mm² / reverse-polarity protected | Clamp terminals 2.5 mm² / reverse-polarity protected |
Secondary side | ||||
Output current | 350 mA (constant current) | 500 mA (constant current) | 500 mA (constant current) | 700 mA (constant current) |
Output voltage | 14.5 V DC (open-circuit operation) | 8.3 V DC (open-circuit operation) | 4.2 V DC (open-circuit operation) | 4.0 V DC (open-circuit operation) |
Lamp load | 1-4 LEDs (rated current 350 mA, UF = 3.0 ... 3.3 V), series connection | 2 x LED (rated current 500 mA, UF = 2.5 ... 3.5 V), series connection | 1 x LED (rated-current 500 mA), (UF = 2.5...3.85 V) | 1 x LED (rated-current 700 mA), (UF = 2.5...3.85 V) |
Output power (max.) | 4.62 W | 3.2 W | 2.0 W | 2.7 W |
Connection terminals | 1.5 mm² / not reverse-polarity protected | 1.5 mm² / not reverse-polarity protected | 1.5 mm² / not reverse-polarity protected | 1.5 mm² / not reverse-polarity protected |
Maximum line length | 1 m (module – LED) | 1 m (module – LED) | 1 m (module – LED) | 1 m (module – LED) |
Type of mounting | To be mounted in luminaires with protection category I or II | To be mounted in luminaires with protection category I or II | To be mounted in luminaires with protection category I or II | To be mounted in luminaires with protection category I or II |
Degree of protection | IP20 | IP20 | IP20 | IP20 |
Permissible ambient temperature | ta = –20 °C to +50 °C | ta = –20 °C to +50 °C | ta = –20 °C to +50 °C | ta = –20 °C to +50 °C |
Maximal permissible test point temperature | tc = 60 °C | tc = 60 °C | tc = 60 °C | tc = 60 °C |
Dimensions in mm (L x H x W) | 110 x 30 x 21 | 110 x 30 x 21 | 110 x 30 x 21 | 110 x 30 x 21 |
Housing material / Colour | Flame retardant polycarbonate / grey | Flame retardant polycarbonate / grey | Flame retardant polycarbonate / grey | Flame retardant polycarbonate / grey |
Weight | 0.042 kg | 0.042 kg | 0.042 kg | 0.042 kg |
Luminous flux ΦE/ΦN at the end of rated operating time (EBLF) | 100% | 100% | 100% | 100% |
Technical data | V-CG-SLS 28 | V-CG-SLR 350 | V-CG-SLR 28 |
Primary side (data valid for full load) | |||
Rated voltage ranges | 220 - 240 V, 50/60 Hz / 176 - 275 V DC | 220 - 240 V, 50/60 Hz / 176 - 275 V DC | 220 - 240 V, 50/60 Hz / 176 - 275 V DC |
Standby power loss | < 0.5 W (230 V / 50 Hz) | < 0.5 W (230 V / 50 Hz) | < 0.5 W (230 V / 50 Hz) |
Current consumption 220 V DC | 35 mA (230 V AC) / 20 mA (220 V DC) | 36 mA (230 V AC) / 22 mA (220 V DC) | 35 mA (230 V AC) / 20 mA (220 V DC) |
Power input | 8.1 VA (230 V AC) | 8.2 VA (230 V AC) | 8.1 VA (230 V AC) |
Power factor | 0.45 ... 0.60 | 0.60 ... 0.70 | 0.45 ... 0.60 |
Inrush current | ≤ 1.5 A | ≤ 1.5 A | ≤ 1.5 A |
Operating frequency | 132 kHz | 132 kHz | 132 kHz |
EEI | A2 | A2 | A2 |
Connection terminals | Clamp terminals 2.5 mm² / reverse-polarity protected | Clamp terminals 2.5 mm² / reverse-polarity protected | Clamp terminals 2.5 mm² / reverse-polarity protected |
Secondary side | |||
Output current | 110 mA (Maximum current) | 350 mA (constant current) | 110 mA (Maximum current) |
Output voltage | 28 V DC (Constant voltage) | 350 mA (constant current) | 28 V DC (Constant voltage) |
Lamp load | LED strip with own current control for 28 V DC and max. 110 mA | 1-3 LED (rated current 350 mA, UF = 3.0 ... 4.0 V), series connection | LED strip with own current control for 28 V DC and max. 110 mA |
Output power (max.) | 3.1 W | 4.2 W | 3.1 W |
Connection terminals | 1.5 mm² / not reverse-polarity protected | 1.5 mm² / not reverse-polarity protected | 1.5 mm² / not reverse-polarity protected |
Maximum line length | 1 m (module – LED) | 1 m (module – LED) | 1 m (module – LED) |
Type of mounting | To be mounted in luminaires with protection category I or II | For installation in a flush-mounted switch box. According German standard DIN 49073 (Ø 60 mm, height min. 61 mm) | For installation in a flush-mounted switch box. According German standard DIN 49073 (Ø 60 mm, height min. 61 mm!) |
Degree of protection | IP20 | IP20 | IP20 |
Permissible ambient temperature | ta = –20 °C to +50 °C | ta = –20 °C to +40 °C | ta = –20 °C to +50 °C |
Maximal permissible test point temperature | tc = 70 °C | tc = 70 °C | tc = 70 °C |
Dimensions in mm (L x H x W) | 110 x 30 x 21 | 41.5 x 57.4 x 43.5 | 110 x 30 x 21 |
Housing material / Colour | Flame retardant polycarbonate / grey | Flame retardant polycarbonate / grey | Flame retardant polycarbonate / grey |
Weight | 0.042 kg | 41.5 x 57.4 x 43.5 | 0.042 kg |
Luminous flux ΦE/ΦN at the end of rated operating time (EBLF) | 100% | 100% | 100% |