The detector features two parts: a transmitter-receiver and reflector. The transmitter-receiver directs a continuous infra-red beam towards the reflector which utilising a prism then sends back the beam to the transmitter-receiver which in turn registers the strength of the beam.
A fire or fault is signalled when the continuous beam is interfered between the two parts by smoke; reducing the strength of the beam. The transmitter-receiver is preset to indicate a fire or fault when the beam's strength is below a certain value.
Your search "" did not match any documents or products.
Description | Cooper | JSB |
Menvier |
Reflective beam detector (50m range) | MAB50R | MAB50R | MAB50R |
Reflective beam detector (100m range) | MAB100R |
MAB100R | MAB100R |
Mounting bracket for reflective beam detector | MRBFP | MRBFP | MRBFP |
Standards: | EN54 Pt12 & Pt17 2002 |
Operating Voltage: | 18Vdc to 30Vdc |
Quiescent Current: | <5mA (no LED's Illumined) |
Alarm Current: | <9mA |
Alignment Current: | <18mA |
Power Up Time: | 10 seconds (approx.) |
Operating Range: | MAB100R - 50 to 100 metres MAB50R - 5 to 50 metres |
Tolerance to Beam Alignment at 35%: | Detector ±0.8°, Prism ±5.0° |
Fire Alarm Thresholds: | 2.50dB (25%) 3.74dB (35%) 6.02dB (50%) |
Optical Wavelength: | 880nm |
Operating Temperature: | -10°C to +55° C |
Operating Width: | 15 metres |
Construction: | PC / ABS |
Colour: | White & Black |
Dimensions (HxWxD): | 210mm x 130mm x 120mm |
Weight: | 0.8kg |
Ingress Protection: | IP40 |
Suitable for use with: | Eaton Addressable Fire System |