Fire detection systems

Optical smoke beam detector for conventional fire systems

Eaton's Optical Smoke Beam Detector for conventional fire alarm systems is designed to replace individual point detectors in large, open areas, such as warehouses.

Extremely simple to install, the beam detector features a built in laser pointer and digital display for easy alignment. Fire and fault conditions are signalled to the control panel using standard wiring, so no additional interconnection is required.

To meet the requirements of multiple applications the detector has four adjustable distance ranges and three sensitivity settings.
Simple setup
Simple setup mode enables easy alignment during installation.
Compliant
Meet the requirements of EN54 part 12
Rapid
Single device installed instead of numerous point detectors

Reflective beam technology: cost-effective smoke detection for large, open areas

The detector features two parts: a transmitter-receiver and reflector. The transmitter-receiver directs a continuous infra-red beam towards the reflector which utilising a prism then sends back the beam to the transmitter-receiver which in turn registers the strength of the beam. 

A fire or fault is signalled when the continuous beam is interfered between the two parts by smoke; reducing the strength of the beam. The transmitter-receiver is preset to indicate a fire or fault when the beam's strength is below a certain value. 

Detectors that speak to the panel with ease of connection

The optical beam detector for use with Eaton conventional fire systems, operate using standard loop wiring. Thanks to their loop interconnectivity, fire and fault conditions are signalled directly to the conventional control panel, removing the need for any additional connections. They also have a simple set up mode enabling easy and quick alignment during installation.

Built in quick test

To help you with testing, each reflective beam detector is supplied with a test filter to simulate required smoke obscuration levels. This will help you to quickly confirm that any reflective beam detectors, that you install, are operating correctly.

Project perfect, view our full range of conventional fire alarm devices

Specifications
Highlight differences
Show only differences
Hide blank features
Looking for Cooper, JSB or Menvier?

Product codes

Reflective Beam Detector (50m Range) MBD50R
Reflective Beam Detector (100m Range) MBD100R
Mounting Bracket MRBFP

Technical specifications

Standards: EN54 Pt12
Operating Voltage: 18Vdc to 30Vdc
Quiescent Current: <5mA (no LEDs illuminated)
Alarm Current: <9mA
Alignment Current: <18mA
Power up Time: 20 seconds (approx.)
Operating Range: 5 to 50 metres (MBD50R) 
5 to 100 metres (MBD100R)
Fire Alarm Thresholds: 2.50dB (25%) 3.74dB (35%) 6.02dB (50%)
Optical Wavelength: 880nm
Operating Temperature: -10°C to +55°C
Humidity (Non-condensing): 0 to 93% RH
Construction: PC / ABS
Colour: White
Dimensions (HxWxD): 210mm x 130mm x 120mm
Weight: 0.8kg
Ingress Protection: IP40
Suitable for use with: Eaton Conventional Fire Systems