Download document () of 20
Discontinued
Fire detection systems

JSB FX4200 conventional control panels

This product has been discontinued and is no longer available. For technical support contact FireTechSupport@Eaton.com.

The JSB FX4200 range are high specification conventional control panels designed for a wide variety of building types and sizes. Available in a choice of 2, 4 and 8 zone versions, the FX4200 range is designed for ease of installation and simple operation.

The FX4200 range are easy to use, with a simple “one-shot” test facility to ensure regular mandatory testing can be quickly and regularly accomplished. Other standard features, such as class change, zone or sounder circuit disabling and programmable relay output facilities complete a highly competitive solution.

Discover our fire systems and devices, and voice alarm product ranges

Specifications

This product has been discontinued and is no longer available. For technical support contact FireTechSupport@Eaton.com.

PRODUCT CODES

Conventional 2 zone control panel FX4202
Conventional 4 zone control panel FX4204
Conventional 8 zone control panel FX4208

TECHNICAL SPECIFICATIONS

Code

FX4202

FX4204

FX4208

Description

2 Zone control panel

4 Zone control panel

8 Zone control panel

Standards

EN54 Pt2 & Pt4 1998,

EN50130 Pt4:1996, EN500081 Pt1:1992 & EN61000 Pt2:1994

EN54 Pt2 & Pt4 1998,

EN50130 Pt4:1996, EN500081 Pt1:1992 & EN61000 Pt2:1994

EN54 Pt2 & Pt4 1998

Specification

Number of Zones

2

4

8

Number of Detectors per Zone

20

20

32

Number of Alarm Circuits

2

2

2

Alarm circuit load

150mA per circuit. 300mA total

400mA per circuit. 800mA total

400mA per circuit. 800mA total

End of Line Devices

Detection circuits: EOLM-1 monitoring unit.

Alarm lines: 6.8K resistor

Detection circuits: EOLM-1 monitoring unit.

Alarm lines: 6.8K resistor

Detection circuits: EOLM-1 monitoring unit.

Alarm lines: 6.8K resistor

Auxiliary Fire Signal/Fault Output

Single pole changeover contacts ratings: 5A 24V dc

Single pole changeover contacts ratings: 5A 24V dc

Changeover contacts ratings: 5A 24V dc

Auxiliary dc output

24V dc fused. 30mA

24V dc fused. 30mA

24V dc fused. 30mA

Mains Input Voltage

230V ac +10%-15%

230V ac +10%-15%

230V ac +10%-15%

Operating Voltage

24V dc

24V dc

24V dc

Standby Duration

24 hours

24 hours

24 hours

Battery

1 x 12V 4Ah (sealed lead acid battery)

1 x 12V 4Ah (sealed lead acid battery)

1 x 12V 7Ah (sealed lead acid battery)

Recharge Period

24 hours

24 hours

24 hours

Environmental

Operating Temperature

-5°C to +40°C

-5°C to +40°C

-5°C to +45°C

Humidity (non condensing)

0 to 75% RH

0 to 75% RH

0 to 75% RH

Physical

Construction

ABS / Polycarbonate front and metal back box

ABS / Polycarbonate front and metal back box

ABS / Polycarbonate front and metal back box

Dimensions (H x W x D)

300mm x 300mm x 74mm

300mm x 300mm x 74mm

270mm x 395mm x 90mm

Weight

4.8kg

4.8kg

7kg

Cable Entry

Top: 10 x 20mm conduit entries Bottom: 1 x 20mm conduit entry (mains cable)

Back: 1 x mains cable entry slot

Top: 10 x 20mm conduit entries Bottom: 1 x 20mm conduit entry (mains cable)

Back: 1 x mains cable entry slot

Top: 18 x 20mm entries Back: cable entry aperture

Download Links

This product has been discontinued and is no longer available. For technical support contact FireTechSupport@Eaton.com.