The Menvier MF9300 is a range of high specification conventional control panels designed for a wide range of building types and sizes.

Available in a choice of 2, 4, 8 or 16 zone versions, the MF9300 range is designed for ease of installation and simple operation.

All panels can be either surface or flush mounted, without the need of additional bezels or back boxes. System flexibility is emphasised by the availability of matching repeater panels for the 4, 8 and 16 zone panels.

Discover our fire systems and devices, and voice alarm product ranges

Specifications

This product has been discontinued and is no longer available. For technical support contact FireTechSupport@Eaton.com.

PRODUCT CODES

Conventional 2 zone control panel MF9302
Conventional 4 zone control panel MF9304
Conventional 8 zone control panel MF9308
Conventional 16 zone control panel MF9316
Conventional 8 zone control panel (24 hour standby) MF9308L 
Conventional 16 zone control panel (24 hour standby) MF9316L
Conventional 8 zone repeater panel MFR9308
Conventional 16 zone repeater panel MFR9316 

TECHNICAL SPECIFICATIONS

Code

MF9302

MF9304

MF9308

MF9316

Description

2 zone control panel

4 zone control panel

8 zone control panel

16 zone control panel

Standards

EN54 Pt2 & Pt4 1998

EN54 Pt2 & Pt4 1998

EN54 Pt2 & Pt4 1998

EN54 Pt2 & Pt4 1998

Specification

 

 

 

 

Number of Zones

2

4

8

16

Detectors per Zone

32

32

32

32

Number of Alarm Circuits

2

2

4

4

Alarm Circuit Load

500mA per circuit. 1A total

500mA per circuit. 1A total

500mA per circuit. 2A total

500mA per circuit. 2A total

End of Line Devices

Detection circuits: 12KΩ⏐resistor

Detection circuits: 12KΩ resistor

Detection circuits: 12KΩ⏐resistor

Detection circuits: 12KΩ⏐resistor

Auxiliary Fire Signal Output

1A 24V dc (resistive) single pole

1A 2 4V dc (resistive) single pole

1A 24V dc (resistive) single pole

1A 24V dc (resistive) single pole

Auxiliary Fault Output

N/A

1A 2 4V dc (resistive) single pole

1A 24V dc (resistive) single pole

1A 24V dc (resistive) single pole

Auxiliary Common Output

24V dc pull to 0V. Max 10mA

24V dc pull to 0V. Max 10mA

24V dc pull to 0V. Max 10mA

24V dc pull to 0V. Max 10mA

Auxiliary dc Output

24V dc fused. 100mA

24V dc fused. 100mA

24V dc fused. 350mA

24V dc fused. 350mA

Repeater output

N/A

2 wire serial link

2 wire serial link

2 wire serial link

Mains Input Voltage

230V ac ±10%. 50/60Hz

230V ac ±10%. 50/60Hz

230V ac ±10%. 50/60Hz

230V ac ±10%. 50/60Hz

System Operating Voltage

24V dc

24V dc

24V dc

24V dc

Standby Duration

72 hours

72 hours

72 hours (24 hours option)

72 hours (24 hours option)

Battery

2 x 7Ah sealed lead acid battery

2 x 7Ah sealed lead acid battery

2 x 12Ah sealed lead acid battery

2 x 12Ah sealed lead acid battery

Recharge Period

24 hours

24 hours

24 hours

24 hours

Environmental

 

 

 

 

Operating Temperature

-5°C to +40°C

-5°C to +40°C

-5°C to +40°C

-5°C to +40°C

Humidity (Non Condensing)

0 to 75% RH

0 to 75% RH

0 to 75% RH

0 to 75% RH

Physical

 

 

 

 

Construction

ABS/Polycarbonate housing & back box

ABS/Polycarbonate housing & back box

ABS/Polycarbonate housing & steel back box

ABS/Polycarbonate housing & steel back box

Dimensions (H x W x D)

344mm x 395mm x 95mm

344mm x 395mm x 114mm

386mm x 395mm x 114mm

386mm x 395mm x 114mm

Weight

10.6kg

10.6kg

16.8kg (24 hours option 16.0kg)

16.9kg (24 hours option 16.0kg)

Ingress Protection

IP20

IP20

IP20

IP20

Cable entries

Top: 13 x 20mm knockouts

Top: 13 x 20mm knockouts

Top: 27 x 20mm knockouts

Top: 27 x 20mm knockouts 