Voltage class
MaxiShrub & Shrubline: 10-167 kVA; Ranch Runner: 10-50 kVA
AWR slash ratings
55/75 °C and 65/75 °C
Average winding rise (AWR)
75˚ C

Core features

Better manage temporary overload capacity

PEAK single-phase pad-mounted transformers can be loaded continuously 9% beyond full rated base load, helping utilities to more precisely size transformers based on periods of peak demand, without accelerated reduction of insulation life.

Gain additional load capacity

Designed to accommodate heavier base loading for longer periods without accelerating loss of insulation system life, PEAK pad-mounted transformers can be loaded continuously 9% beyond full rated base load.

Improve reliability

With superior moisture and thermal stress managing capabilities, PEAK pad-mounted transformers extend insulation system life, improving overall system reliability by reducing outages and transformer failures.
Specifications

Ratings

  • Overload capacity: At least 109%
  • Standard with Envirotemp FR3 dielectric fluid
  • MaxiShrub 50 or 60 Hz (10-167 kVA)
    • Primary voltage: 2400-34,500 V
    • Secondary voltage: 120-600 V
    • ANSI Type-1 frontplate
  • Shrubline 50 or 60 Hz (10-167 kVA)
    • Primary voltage: 2400-19,920 V
    • Secondary voltage: 120-600 V
    • ANSI Type-2 frontplate
  • Ranch Runner 50 or 60 Hz (10-50 kVA)
    • Primary voltage: 2400-14,400 V
    • Secondary voltage: 120-600 V
    • Rural Utilities Services (RUS) approved frontplate

Specifications

  • Meet or exceeds ANSI, NEMA and DOE2016 standards
    • IEEE standards C57.12.00, C57.12.38, C57.12.28, C57.12.35, C57.12.90, C57. 91 and C57.154
    • NEMA standards, NEMA TR 1 (R2000)
    • Department of Energy Efficiency Standard, 10 CFR Part 431
  • Tank coating exceeds IEEE Std C57.12.28-2005 and C57.12.29-2005 standards (stainless steel units only)
  • Full compliance with IEEE Std C57.12.28-2005 standard enclosure integrity requirements
  • Envirotemp FR3 fluid
  • The transformer shall be designed in accordance with this specification and shall have an average winding rise (AWR) of one of the following:
    • 65 °C, 65/75 °C, 75 °C
    • The applicable AWR rating shall be specified on the inquiry
  • The transformer shall be designed in accordance with this specification and shall have one of the following kVA ratings:
    • 10, 15, 25, 37.5, 50, 75, 100, 167
    • The applicable kVA rating shall be specified on the inquiry
  • Quality System ISO 9001 certified