Eaton Cooper Power series Shrubline VFI vacuum switchgear provides fault interruption and convenient load switching for underground systems up to 25 kV. Additionally, the switchgear is designed for outdoor mounting on a concrete pad and employs oil as the insulation medium to provide a compact, low-profile installation.
15kV | 25kV | |
Maximum design voltage, kV |
15.5 | 27 |
BIL, kV |
95 | 125 |
1-Minute withstand (60 Hz) interrupter and terminators, kV |
34 | 40 |
Continuous current (max), A |
200 | 200 |
Interrupting current (sym./asym.), kA |
12/20 | 12/20 |
Momentary current 10 cycles (asym.), kA |
20* | 20* |
3 Sec. (sym.), kA |
12* | 12* |
Making current (sym.), kA |
12 | 12* |
Transformer magnetizing interrupting current, A |
21 | 21 |
Cable charging interrupting current, A |
10 | 25 |
*Interrupter only. Short time-current ratings of bushings are 10 kA (sym.). |
Visit this page for information on earlier models.