Circuit breakers

PL7 xPole Miniature Circuit Breaker

This versatile and safe miniature circuit breaker has a breaking capacity of 10kA. It features a guide for secure terminal connection and is compatible with a standard busbar which can be positioned either above or below.
VERSIONS
1-, 2-, 3-, 4-, 1+N and 3+N pole
RATED CURRENTS
up to 32 A
TRIPPING CHARACTERISTICS
B, C, D

Core features

  • High-quality miniature circuit breakers for commercial and residential applications
  • 3-position DIN rail clip, permits removal from existing busbar system
  • Contact position indicator red - green
  • Guide for secure terminal connection
  • Comprehensive range of accessories suitable for subsequent installation
  • Rated currents up to 63 A
  • Tripping characteristics B, C, D
  • Rated breaking capacity of 10 kA according to IEC/EN 60898-1

The most commonly used type of overcurrent protection device

MCBs protect cables against damage due to overload and short circuits: In the event of dangerously high currents, the circuit breaker’s bimetallic thermal release will disconnect the power supply. In the event of a short circuit, the electromagnetic release will disconnect the power supply in a timely manner.

A design that is standard-compliant and quality-tested

Eaton’s PL7 miniature circuit breakers are type-tested and approved according to IEC/EN 60898-1. Part 1 of IEC/EN 60898 applies to AC MCBs if the rated voltage between the phases does not exceed 440 V, the rated current does not exceed 125 A and the rated breaking capacity does not exceed 25,000 A.

The right MCB for every application

Circuit breakers with tripping characteristic B are the standard MCB type used for lighting and socket circuits. For circuits with high peak currents (such as motor circuits) devices with tripping characteristic C are used. Circuit breakers with tripping characteristic D are used for circuits with inductive and capacitive loads, such as solenoid valves, transformers or motors.