16 Zone control panel for conventional fire systems

Eaton's 16 zone conventional control panel features an array of user-friendly features and is available at very competitive prices.

The attractive flush or surface mountable plastic enclosure with a metal back box has been designed through intensive voice of the customer research to provide ample space for termination of cables.

The system is suited to medium-sized commercial builds including hotels, restaurants, retail units, care homes, warehouses and supermarkets.

No. of zones
16
Detectors per zone
30
No. of alarm circuits
4

Contemporary, compact panel for the largest conventional fire alarm systems

Developed with extensive user feedback, Eaton's 16-zone conventional fire alarm panel is modern, slim and easy to use.

Its clean white housing was chosen to complement contemporary interiors of building old or new, whilst initiative 6 button interface and LED indicators are designed to be easy to use and diagnose with.

Eaton 16 Zone Conventional Panel left, right and centre

Supervisor mode - Secure access to fast weekly one man testing

Featuring a normal and supervisor mode facility, the panels supervisor mode can be accessed with a 4 digit security code to prevent unauthorised use. In the mode, a one-shot weekly test function can be initiated by the facility manager enabling time for a call point to be put into fire condition and correctly reported on the panel. After which the system automatically resets and returns to its normal state.

Project perfect, view our full range of conventional fire alarm devices

Specifications

Product codes

16 Zone control panel for conventional fire alarm systems CF50016

Technical specifications

Description: 16 zone control panel  
Standards: EN54 Pt2 1998, A1:2006
EN54 Pt4 1998, A1:2002 +A2 2006
 
Number of Zones: 16  
Detectors per Zone: 30  
Number of Alarm Circuits: 4  
Alarm Circuit Load: 150mA per circuit, 0.3A total / 400mA per circuit, 0.8A total / 500mA per circuit, 2A total  
End Of Line Devices: Detection circuits: EOLM-1
Monitoring unit Alarm lines: 6.8Ω resistor
 
Auxiliary Fire Signal / Fault Output: 1A 24V dc single pole changeover contacts  
Auxiliary DC Output: 50mA  
Mains Input Voltage: 230Vac - 15% +10%  
System Operating Voltage: 24Vdc  
Standby Duration: 24 hours  
Operating Temperature: 5°C to +55°C  
Humidity (Non-condensing): 0 to 75% RH  
Construction: Polycarbonate housing & metal box  
Dimensions (HxWxD): Surface: 276,mm x 375mm x 136mm
Cut-Out: 232mm x 335mm x 96mm
 
Weight: 6.8kg  
Ingress Protection: IP30  
Cable Entry: Top: 12x20mm entries with blanking plugs
Rear cable entry aperture
 