Download document () of 20
Fire detection systems

ULCF3000 - UL Addressable fire system panel

Eaton's ULCF3000 is a high specification analogue, wall or rack mounted UL listed fire alarm system control panel available in 2 or 4 loop configurations. It combines sophisticated functionality with simple operation and aesthetically pleasing design.

Supporting complex cause and effect programming and a wide range of user-controllable functions, the system is ideal for a diverse range of projects, from industrial applications through to large multi-site commercial developments. 

Utilising soft addressing to minimise installation and remove the potential for error associated with manual addressing, each of Eaton's devices and components has been specifically designed to work with the ULCF3000 panel. Meaning all the detectors,  interfaces and ancillaries are all fully compatible with each other and that the full range of system functionality is supported by each device.

Event History
Stored with date and time stamp
System
Optional integral printer
Loops
2 or 4 Class A Style 7 SLC loops

Less time troubleshooting and programming, more time winning other contracts

Eaton's ULCF3000 is designed for ease of operation, featuring a large versatile touch-screen user interface and a menu-driven graphical user interface. The control panel minimizes programming and troubleshooting time by using a range of features such as auto config, walk test and system details menu.

Flexibility in design, flexibility in commissioning

Supporting auto learn functions as well as a comprehensive range of soft addressing modules and devices, the ULCF3000 offers flexibility in design and reduced commissioning time. The panel features 4 notification appliance circuit (NAC's) outputs and dedicated alarm, trouble and AC trouble relays.

Up to 800 devices per panel, all specifically designed to work together

Each of the system components have been specifically designed to operate as part of a ULCF3000 UL Listed system providing assurance that the panel, detectors, interfaces and the ancillaries are all fully compatible with each other and that the full range of system functionality is supported by each device. The control panel has a full network capability up to 126 panels, and up to 200 addresses per loop.

Discover our UL addressable product range

Specifications

Product codes

2 Loop Panel ULCF30002G
4 Loop Panel ULCF30004G
2 Loop, Integral Printer ULCF30002GP
4 Loop, Integral Printer ULCF30004GP
2 Loop, Network Card  ULCF30002GNC
4 Loop, Network Card ULCF30004GNC
2 Loop, Integral Printer, Network Card ULCF30002GPNC
4 Loop, Integral Printer, Network Card ULCF30004GPNC
2 Loop, Red Metal Box ULCF30002GRM 
4 Loop, Red Metal Box ULCF30004GRM
2 Loop, Integral Printer, Red Metal Box ULCF30002GPRM
4 Loop, Integral Printer, Red Metal Box ULCF30004GPRM
2 Loop, Integral Printer, Network Card, Red Metal Box ULCF30002GPNCRM
4 Loop, Integral Printer, Network Card, Red Metal Box ULCF30004GPNCRM
Rack Mounted 2 Loop c/w Network Card ULR3000L2NC
Rack Mounted 4 Loop c/w Network Card ULR3000L4NC
Loop Connected Repeater Panel ULCF3000PR
Touchscreen Network Repeater Panel ULCTPR3000

Technical specifications

Description: UL Intelligent Addressable Control Panel
Standards: UL864 9th edition
Primary Operating Supply: 120Vac / 240Vac, 60Hz, 2.0A supervised
 
Secondary operating supply
Battery Voltage: 24Vdc
Battery Charge Current: 1.0A (max)
Battery Derating Factor: 0.1
Battery Capacity Supervised: 12Ah (max)
 
Notification appliance circuits Class B, Style Y, Sounder Group 1, Sounder 1, Sounder Group 1, Sounder 2, Sounder Group 2
Output Voltage: 24Vdc
Output Current: 0.75A (max)
Line Impedance: 50Ω
When powered by 240Vac, the maximum current of 3.0A is shared between these circuits
When powered by 120Vac, the maximum current of 2.25A is shared between these circuits
Supervised, power limited, regulated
 
Notification appliance circuits Class B, Style Y, SYNC MODULE. NAC1, NAC2
Output Voltage: 24Vdc
Output Current: 0.5A (max)
Line Impedance: 50Ω (max)
The maximum current of 0.5A is shared between these circuits
Supervised, power limited, regulated
 
Alarm, trouble contacts. Relay expansion
Unity Power Factor: 30Vdc For connection to power limited sources only
Unity Power Factor: 30Vdc, 1A For connection to power limited sources only
   
Aux relay (AC Trouble) contacts
Rated Voltage: 24Vdc
Maximum Current: 500mA
Line Impedance: 50Ω (max)
Supervised, power limited
 
Network SLC
Voltage: 5Vdc
Current: 100mA (max)
Line Impedance: 50Ω (max)
Power limited
Limited to same enclosure installations
Suitable for use with: Eaton UL fire systems
Download Links