To meet the growing challenges of quality and continuity in distribution systems, the NOVA LBS automatic load break switch offers greater possibilities, allowing the automation of distribution through intelligent sectioning.
Rated voltage | 15 / 27 kV |
Rated lightning impulse withstand voltage | 125 kV |
Rated power-frequency withstand voltage | |
Dry, one minute | 60 kV |
Wet, ten seconds | 50 kV |
Rated normal current | 630 A |
Rated short-time withstand current | 16 kA (3s) |
Rated peak withstand current | 41,6 kA |
Rated line-charging breaking current | 2 A |
Rated cable-charging breaking current | 20 A |
Mechanical endurance operations | 10.000 |
Electrical endurance class | E3 |
Mechanical endurance class | M2 |
Mass (Weight) – Switch only | 105 kg (231 lbs) |
Mass (Weight) – Switch and control | 135 kg (298 lbs) |