The VoCALL 5 emergency voice communication panel (EVCS) is an ideal panel for smaller installations which require up to 5 outstations or emergency assist alarms. The system comprises the Compact 5-line unit which controls up to 5 outstations (Type A, Type B, Emergency Assist Alarms or, in regions which allow their use, roaming handsets and jack plates).
The standalone unit contains the systems master handset, power supply and connectivity for the 5 outstations. 20mm knockouts are provided for all system cabling and the housing is of ample size to support 2x 5Ah backup batteries (not supplied).
The unit is microprocessor controlled but requires no on-site programming; it is fitted with end of line resistors which are simply discarded when an outstation is connected making installation quick and simple.
The VoCALL 5 system uses star topology cabling which means that the outstations are wired directly to the panel using 2 core radial fire rated enhanced cables.
The EFVCC5 panel also includes 20mm knockouts for ease of cabling.
This simple panel design and cabling technique ensures simple and fast installation, meaning that your project can be completed quickly using minimum resources.
VoCALL 5 surface mount - EFVCC5.
VoCALL 5 optional stainless steel flush mount cover - EFVCC5-FC
Fitted optional cover ready for flush fitting
VoCALL suits all sizes of installation from one and two outstation systems in small shops like Bon Marche, to a massive 364 line dual network system at Westfield Shopping Centre in London’s White City.
Over the years VoCALL has been installed on several high profile projects in some of the world’s most prestigious sites, from Wimbledon AELTCC and St Pancras stations in the UK to the Marina Towers and Jumeirah Tunnel in the Middle East.
VoCALL 5, compact 5 line unit - surface mount |
EFVCC5 |
VoCALL 5, compact 5 line unit - stainless steel flush mount cover |
EFVCC5-FC |
VoCALL 5, compact 5 line unit - semi flushing bezel | EFVCC5-FB |
Power supply | |
Voltage: | 230V ac +/- 10% 50/60Hz |
Internal power supply: | 24V dc |
Supply and battery: | Monitored, open, short, fuses |
Protection: | Deep discharge, short, thermal |
Battery size and type: | 2 x 12V VRSLA 5Ah (not supplied) |
Mains fuse: | 240V 2A HRC |
Battery fuse: | 1A PTC |
Charge current: | 250mA (max) |
Inputs | |
Number of lines: | 5 |
Remote enable: | Short to use |
Outputs | |
Number: | 2 (fault & in-use) |
Type: | Volt free relay |
Contact: | 30V dc 1A |
Controls | |
Buttons: | 5 zone keys, 1 mute buzzer |
Zone LEDs (x5): | 1 line status,1 fault status per zone |
Supply: | LED AC & DC |
Fault LEDs: | 4 (General, System, Master, PSU) |
Outstation cables | |
Type: | Fire rated (Some installations will require enhanced cabling, see local regulations for guidance.) |
Cores: | 2 Core (1mm or 1.5mm) |
Distance (max): | 300m |
Physical | |
Weight: | 6.5kg |
Installation | |
Mounting: | Surface or optional stainless steel flush mount |
Cutout: | 330mm x 300mm (semi-recessed unit) |
Cable entries: | Top: 7 x Cable knockouts (20mm) |