Download document () of 20
Automatic transfer switches

Breaker-Based Bypass Isolation Transfer Switches

The Eaton Breaker Type Bypass Isolation Switch is designed to require minimum maintenance even under the most strenuous of operating conditions. Due to the use of moulded case switches and their inherent self-protection capability, the contact structure and mechanism is extremely long lived.

Continuous Current Rating
Up to 1000A
System Voltage Rating
Up to 600 Vac
System Frequency Rating
50/60 Hz

Core features

  • Auxiliary relay contacts:
    • Source 1 Present 2NO & 2NC
    • Source 2 Present 2NO & 2NC
  • Switch position indication contacts:
    • Source 1 Position 1NO & 1NC
    • Source 2 Position 1NO & 1NC
  • Source 1 & Source 2 sensing:
    • Undervoltage/underfrequency
    • Overvoltage/overfrequency
    • 3-phase rotation protection
    • 3-phase voltage unbalance/loss
  • Pre-transfer signal contacts 1NO/1NC.
  • Go to Emergency (Source 2).
  • Seven field programmable time delays.
  • LCD-based display for programming, system diagnostic and Help message display.
  • Mimic diagram with source available and connected LED indication.
  • System test pushbutton.
  • Programmable plant exerciser.
  • Safe manual operation under full load with permanently affixed operating handle.
  • Monitor Utility and Generator power source voltages and Generator power source frequency.
  • Provides undervoltage protection of the Utility and Generator power sources.
  • Provides underfrequency and overfrequency protection of the Utility and Generator power source.
  • Provides faceplate source status indications.

Transfer switch 101

Read our introductory guide to picking the right transfer switch for your environment

Intelligent monitoring and control

Discover the reliability, intelligence, and programming benefits of Eaton’s ATS controllers

Built with experience

With more than 100 years of experience, Eaton can engineer reliable solutions to meet the specific demands of your application – completely designed and customised to your needs

You may also be interested in

Specifications

Ratings

CONTINUOUS CURRENT Up to 1000A
SYSTEM VOLTAGE Up to 600Vac
SYSTEM FREQUENCY 50/60 Hz
SHORT-CIRCUIT WITHSTAND AND CLOSE-ON Up to 65kA
SHORT-CIRCUIT WITHSTAND AND CLOSE-ON (SPECIFIC FUSE CLASS) Up to 200 kA

Standards

THIRD PARTY APPROVAL/RECOGNITION UL 1008 and CSA 22.2 No. 178 Listed
NEMA 1, 3R, 12, 4X
SEISMIC QUALIFICATION IBC, CBC, UBC Zone 4, OSHPD
EMISSIONS FCC Part 15 (Subpart B); CISPR 11
ELECTROMAGNETIC COMPATIBILITY (EMC)

IEC 61000-4-2: electrostatic discharge immunity

IEC 61000-4-3: radiated immunity

IEC 61000-4-4: fast transient/burst immunity

IEC 61000-4-5: surge immunity

IEC 61000-4-6: conducted immunity

IEC 61000-4-11: voltage dip/interruption immunity

Devices

SWITCHING MECHANISM Double-throw power switch
CIRCUIT PROTECTION Moulded Case Circuit Breaker
SURGE PROTECTION Surge Protective Devices
POWER AND ENERGY METERS Power Xpert, IQ Meters

Enclosure

ENCLOSURE TYPE Indoor and outdoor
ACCESS Front
CABLE ENTRY Top/bottom
MOUNTING Wall
Download Links