Eaton’s Pow-R-Line CS switchboard is the most compact expandable service entrance and distribution solution in Canada. Eaton’s Pow-R-Line CS switchboard is a cost-competitive solution that offers main device, utility metering and distribution in a single cell. Additionally, the switchboard is expandable to include a 75°C or 90°C wireway, sub-main, distribution and fusible switch meter centre cells for a complete offering.
RATED MAXIMUM VOLTAGE | 600 Vac |
CONTINUOUS CURRENT | 1200A |
INTERRUPT RATING | 200 kA |
NEMA | PB-2 |
THIRD-PARTY APPROVAL/RECOGNITION | CSA C22.2 No.31 CSA C22.2 No.244 CSA C22.2 No.229 (FSMC) |
PROTECTION DEVICES |
Moulded case circuit breakers, FDPW, FSMC |
METERS | Power Xpert meter, IQ meters |
SURGE PROTECTION | SPD series |
Device mounting |
Fixed |
ACCESS | Front |
STANDARD INDOOR WIDTH DIMENSIONS | 30, 48 inches |
STANDARD INDOOR DEPTH DIMENSIONS | 12, 18 inches |
STANDARD INDOOR HEIGHT DIMENSION | 90 inches |
OPTIONS |
Door-over-distribution, cross-bus for future expansion |
Wireway: | ||
Direct cable connection or wireway | ||
Wireway rating: | 75°C (standard) 90°C (optional) |
|
Main assembly: | Factory bussing to disconnect or circuit breaker | |
Utility requirement dimensions: | 30 inches width x 30 inches depth | |
Standard indoor enclosure depth dimensions: | 12, 18 or 30 inches (30 inches available only with 30 inches deep) | |
Standard indoor enclosure width dimensions: | 800A: 12, 18, 24, 30 inches 1200A: 24, 30 inches |
|
1200A main/40X distribution cell: | ||
Cable entry: | Top or bottom, left or right | |
100% rated: | 1200A main available with wireway | |
Devices: | metered fusible switches (FSMC), non-metered fusible switches (FDPW) or circuit breakers (not mixed) | |
Standard indoor enclosure depth dimensions: | 12, 18 inches | |
Standard indoor enclosure width dimensions: | 48 inches | |
800A main/40X distribution cell: | ||
Cable entry: | Top or bottom, left or right | |
100% rated: | 800A main available with wireway | |
Devices: | non-metered fusible switches (FDPW) or circuit breakers (not mixed) | |
Standard indoor enclosure depth dimensions: | 12, 18 inches | |
Standard indoor enclosure width dimensions: | 30 inches | |
50X distribution cell: | ||
Chassis: | Pow-R-Line 1a/2a | |
Devices: | metered fusible switches (FSMC), non-metered fusible switches (FDPW) or circuit breakers (not mixed) | |
Standard indoor enclosure depth dimensions: | 12, 18 inches | |
Standard indoor enclosure width dimensions: | 30, 38, 48 inches (depending on feeder device configuration & amperage) | |
Sub-main cell with 600A max. breaker: | ||
80% rated: | Sub-main disconnect | |
Included: | reverse fed breaker, utility metering compartment and outgoing lugs, field wiring connection compartment | |
Standard indoor enclosure depth dimensions: | 12, 18 inches | |
Standard indoor enclosure width dimensions: | 30 inches |