Eaton's Pow-R-Line Xpert 1X-LX (PRL1X-LX) and Pow-R-Line Xpert 2X-LX (PRL2X-LX) column panelboards provide higher interrupting ratings for selective coordination purposes and a compact and flexible solution for electric power distribution with integrated breakers, metering and surge protection. Additionally, they’re designed to meet CSA 22.2 No. 29 and NEMA PB1 standards for use in data centres, industrial, commercial and healthcare facilities.
Find out how intelligent circuit protection for panelboards and switchboards can provide accurate, actionable data to increase efficiency.
Dig into the features and functionality to find out how incorporating intelligent circuit protection for panelboards and switchboards can provide accurate, actionable data to increase efficiency.
For a deep insight into the Pow-R-Line Xpert family, view our video series covering these topics:
RATED MAXIMUM VOLTAGE | 600 Vac and 250 Vdc |
CONTINUOUS CURRENT | 100-225A |
INTERRUPTING RATING | 240 Vac: 65 kA fully rated 240 Vac: 100-200 kA series rated 480Y/277 Vac: 14 kA fully rated 480Y/277 Vac: 22-150 kA series rated 250 Vdc: 10 and 14 kA fully rated 600 Vac: 10 kA fully rated 600 Vac: 35 kA series rated |
NEMA | PB-1 |
THIRD-PARTY APPROVAL/RECOGNITION | CSA C22.2 No. 29 |
SEISMIC QUALIFICATION | Lighting and appliance panelboards certificate |
PROTECTION DEVICES | Moulded case circuit breakers and miniature circuit breakers |
DEVICE MOUNTING | Bolt-on |
ACCESS | Top and bottom access |
ENCLOSURE TYPE | NEMA Type 1 |
STANDARD INDOOR WIDTH DIMENSIONS | 8.63 inches |
STANDARD INDOOR DEPTH DIMENSION | 6.00 inches |
STANDARD INDOOR HEIGHT DIMENSION | 69, 78, 81, or 90 inches |
CUSTOM DIMENSIONS AVAILABLE | Contact satellite manufacturing facility |