Eaton’s metal-enclosed breaker (MEB) switchgear consists of a single, high-drawout vacuum circuit breaker (Type VCP-W) in a metal-enclosed cabinet.
When deployed as primary protection for a single-ended substation, the MEB can eliminate the need for a secondary main circuit breaker. It can also be applied as the primary main device and integrated with fused or unfused feeder switches in Eaton metal-enclosed switchgear. The MEB 5/15kV switchgear meets or exceeds all required industry standards (IEEE, ANSI and NEMA).
The metal-enclosed breaker (MEB) can be applied in a variety of configurations:
RATED MAXIMUM VOLTAGE | 4.76 kV, 15 kV | |
CONTINUOUS CURRENT | 600 A to 2000 A | |
INTERRUPT RATING | Up to 63 kA rms symmetrical | |
BASIC IMPULSE LEVEL (BIL) | 4.76 kV class – 60 kV peak, 15 kV class – 95kV peak |
ANSI/IEEE STANDARD | C37.20.3, C37.20.4, C37.22, C37.57, C37.58 | |
NEMA | SG-5, SG-6 | |
CSA | C22.2 No. 31-04 | |
THIRD-PARTY APPROVAL/RECOGNITION | UL, CSA available for most ratings | |
SEISMIC QUALIFICATION | IBC, CBC |
ACCESS | Front & rear options | |
INSULATING MEDIUM | Air | |
BUS INSULATION | Optional | |
BUS SUPPORTS | Glass polyester | |
ENCLOSURE TYPE | Indoor & outdoor |
|
INDOOR SECTION DIMENSIONS (TYPICAL) | 914mm (36") w x 2032mm (80") d x 2296mm (90") h |
SWITCHING DEVICE | Vacuum circuit breaker | |
DEVICE MOUNTING | Drawout |
WEIGHTS | 726 kg (1600 lbs) | |