Reclosers

6H, V6H three-phase reclosers

Eaton's Cooper Power series 6H and V6H three-phase, hydraulically controlled reclosers provide reliable, self-contained distribution-circuit overcurrent protection. Additionally, they’re offered at low cost and require minimal service.

Hydraulic control
Reduce installation and operation costs
3 self-contained interrupting mechanisms
More compact than comparable designs
Multiple operation sequences
Simplify system coordination

Core features

  • Offers vacuum or oil interruption; adapts three, single-phase interrupting structures with a common lockout mechanism
  • Senses line current in each phase and trips individually; can also lockout all phases if one phase sequences to lockout
  • Initiates tripping with its series-connected coil
  • Offers selection of dual time-current characteristics which permits coordination with other protective devices
  • Provides a non-reclosing feature set with a hotstick-operated lever for one operation-to-lockout without removing the recloser from service

Timing selectivity offers flexibility in application and equipment coordination

Eaton's Cooper Power series 6H and V6H three-phase reclosers are self-contained, hydraulically controlled devices. They sense and interrupt fault currents on a three-phase or per-phase basis. All timing is governed by the hydraulic mechanism which controls the timing before contact opening, establishes the time delay before the contacts reclose, counts the number of operations and causes the recloser to lock out when the preset number of trip operations has been completed.

Timing characteristic and sequence variations

Eaton's Cooper Power series 6H and V6H reclosers provide for multiple operating sequences. They can all be fast, delayed or a combination of fast followed by delayed operations. When a recloser is programmed for both fast and delayed operations, the fast operations – involving no intentional time delay – occur first in the sequence according to the recloser’s A curve time-current characteristic.
Specifications

Standards

Eaton's Cooper Power series reclosers are designed and tested in accordance with the following ANSI standards: C37.60 and C37.85 and ANSI Guide C37.61

Ratings

Recloser 6H V6H
Nominal operating voltage (kV) 2.4—14.4
2.4—14.4
Maximum continuous current (amps)
100 200
Maximum design voltage (kV) 15.5 15.5
Max interrupting current (symmetrical amps)
@ 2.4—4.8 kV
3000 3000
@ 4.8—8.32 kV
2500 2500
@ 8.32—14.4 kV
2000 2000
Impulse withstand (BIL), 1.2x50 sec wave (crest kv) 110 110
60-Hz withstand (rms kV)
Dry, one minute 50 50
Wet, ten minutes 45 45
Reclosing time (sec) 1-1/2 1-1/2
Bushing creepage distance (in.) 10-7/8 10-7/8
Available trip coils - Continuous current rated (amps) 5, 10, 15, 25, 35, 50, 70, 100 5, 10, 15, 25, 35, 50, 70, 100, 140, 200

Duty cycles

Recloser % Interrupting rating Maximum circuit X/R ratio Number unit operations Total unit operations
6H 15-20
2 32 68
45-55
5 24
90-100
10 12
V6H 15-20
2 128 272
45-55
5 96
90-100
10 48

Optional accessories

  • Lockout and lockout indication
    • Lockout-indicating switch
    • Shunt-lockout mechanism
    • Ground-fault lockout
  • Bushings
    • 17-in.-creepage bushings
  • Bushing current transformer for field installation
    • Slip-on bushing current transformer kit
  • Mounting equipment
    • Double cross-arm bracket or substation hanger
    • Substation mounting frame
    • In-line broadside pole-mounting hanger
    • Surge arrester mounting bracket
    • Tank-lifting windlass for substation mounting frame