Eaton's Cooper Power series D and DV hydraulically controlled automatic circuit reclosers provide reliable, economical overcurrent protection for distribution systems. Additionally, the reclosers use oil as the arc-interrupting medium and provide single-phase load protection, tripping and automatic clearing of temporary faults.
Recloser | D | DV | |
Nominal voltage (kv) |
2.4-14.4 |
24.9-34.5 |
|
Maximum design voltage (kv) |
15.5 | 38 | |
Impulse withstand (BIL), 1.2 x 50 microsecond wave, crest (kv) |
110 | 150 | |
60-hz, withstand (kv rms) |
Dry, one minute | 50 | 70 |
Wet, ten seconds | 45 | 60 | |
Maximum continuous current (amps) |
560 | 560 | |
Reclosing time (seconds) |
2 | 2 | |
Bushing creepage distance (inches) |
11-5/8 | 17 |
Trip coil ratings continuous amps |
Minimum trip ratings (amps) |
Interrupting Ratings (rms symmetrical apps) |
|||
Type D |
Type DV |
||||
@4.8 kv |
@8.32 kv |
@14.4 kv |
@24.9, 34.5kv |
||
100 | 200 | 6000 | 6000 | 6000 | 6000 |
140 | 280 | 8400 | 8400 | 8400 | 8000 |
160 | 320 | 9600 | 9600 | 9600 | 8000 |
185 | 370 | 11100 | 10000 | 10000 | 8000 |
225 | 450 | 12000 | 10000 |
10000 |
8000 |
280 | 560 | 12000 |
10000 |
10000 |
8000 |
400 | 800 | 12000 |
10000 |
10000 |
8000 |
400x | 560 | 12000 |
10000 |
10000 |
8000 |
560 | 1120 | 12000 |
10000 |
10000 |
8000 |
560x | 750 | 12000 |
10000 |
10000 |
8000 |
Visit this page for information on earlier models.
Eaton customers can access software, firmware and additional product documentation at My.Eaton.com. To request access, visit My.Eaton.com and complete the registration form. Please note that requests for access can take several days to process. If your matter is urgent, contact the customer support group at 866-975-7347.