Download document () of 20
Reclosers

Form 7 recloser control

Eaton’s Cooper Power series Form 7 recloser control represents the next generation in recloser control technology while continuing to offer the most popular features from previous Cooper Power series recloser controls. The Form 7 control is designed to deliver state-of-the-art intelligence, best-in-class integrated security tools and unparallelled scalability to future-proof your investment. Smarter, faster and more flexible than any predecessor control, the Form 7 control helps utilities enhance reliability and efficiency, reduce operational and maintenance costs, and protect systems against mounting threats – today and well into the future.

Intelligence
Simplified implementation
Embedded security
Intrusion protection
Expandability
Future upgradability

Core features

  • Enhanced processing power, memory capacity and data sampling supports simple to advanced applications using ProView NXG software and WorkBench NXG
  • Extensive diagnostics and communications tools facilitate monitoring and analysis of the system and the control and enable flexible, upgradable communication capabilities
  • Integrated security tools help prevent cyber intrusions and unauthorised access and are capable of evolving to meet emerging threats to the distribution infrastructure
  • Integrated security protocols and encryption secure digital communications, helping to thwart cyberattacks that could disable extensive portions of the distribution grid
  • Modular, flexible and scalable architecture and expansion bays to accommodate easy field upgrades and new feature implementation
  • Expandability facilitates faster development and easier delivery of new features and updates, affording the flexibility and agility to meet today’s requirements and future needs, both planned and unexpected

Technologically advanced features

Eaton’s Form 7 recloser control includes modular, flexible and scalable hardware featuring an 800 MHz quad-core processor, 1 GB RAM and 4 GB flash storage. The control’s modular layout allows you to easily insert hardware as new applications arise and requirements change.

Integrated security tools help prevent local intrusion or unauthorised operation

Eaton’s Cooper Power series Form 7 recloser control includes an array of integrated security tools to help prevent local intrusion or unauthorised operation. This array provides a role-based access control (RBAC) user audit log, signed firmware and an optional door switch (which reports door opening/closing or switch disconnection status). Transport Layer Security (TLS) encryption tools can be used to establish a secure, private communication channel for SCADA traffic and remote connection to ProView NXG.

Simplified training and operator familiarity

Eaton’s Form 7 recloser control’s powerful Workbench NXG provides a highly intuitive graphical user interface that simplifies training and operator familiarity. Workbench NXG logic is readily transparent and provides powerful logic tools that allow you to customise control functions or create powerful, unique applications.
Specifications

Form 7 recloser control ratings and specifications

Description Information
Cabinet rating IP44
Operating temperature range -40°C to +55°C ambient temperature
Heater rating 100 W
Control input power 120 or 240 Vac up to 12 AWG wire size
Power usage (Watts) 15 W (no accessories)
Operating AC voltage range 85–264 Vac universal input
Input fuse ratings Fuses on power supply board: 5A 250 Vac, time delay fuse, 50 A interrupting
Optional input power fuses: 5 A, 250 Vac, time delay fuse, 10 kA interrupting @ 120 Vac, 750 A interrupting @ 250 Vac
Battery rating/back-up power 24 Vdc, 13 AHr. Minimum back-up power 20 hours at 20°C
Battery charge rate 450 mA bulk charge with trickle capability
GFCI rating/max voltage & current 120 Vac only, 15 A fuse. Same fuse used as input power fuse accessory
Instantaneous metering current accuracy*†

IA, IB, IC, IN: +/- 1 mA (from 0.1 A to 2 A)

  • at 0.1 A... (+/- 1.0%)
  • at 2 A... (+/- 0.2%)
PT voltage input range (sensing) 0–285 Vrms, 0-403 Vpeak; 1 Mohm input impedance
LEA voltage input range (sensing) 0–8 Vrms, 0-11.3 Vpeak; 1 Mohm input impedance
Storage temperature range -40°C to +85°C
Contact input rating (voltage)

12 Vdc-250 Vdc: 2mA

12 Vac-240 Vac (248 Vac Maximum): 2mA

Contact output rating (max current value) Refer to catalogue
Auxiliary power supply rating 13.2 Vdc, 40 W continuous (75 W surge)
System frequency 60 Hz
USB host port (left USB) USB 2.0
USB device port (right USB) USB 2.0
* Accuracy specified at 25°C and at nominal system frequency.
† Current measurements listed in secondary amps.