Medium voltage cable accessories

Junctions

Eaton’s Cooper Power series junction bars are designed for vault or apparatus applications and can be used for looping, tapping and sectionalising. 

Unique, efficient sectionalising solutions
Reduced outages
Durable construction and design
Built for harsh conditions
Vault or apparatus applications
Flexible design

Core features

  • Designed and manufactured in accordance with IEEE Std 386 standard
  • Junction bars are manufactured in 200 A, 600 A or 900 A configurations.
  • In-line junctions available from 15 kv to 35 kV in two through six interface configurations
  • Junctions are available with an adjustable stainless steel bracket or “U” straps for mounting flexibility
  • Junctions maybe ordered pre-installed with Cooper Power series sectionalising cabinets 

Reduce outage durations with Cleer 600 A loadbreak

Eaton's Cooper Power series variable and multipoint junctions allow for integration of the Cleer 600 A loadbreak connector system to provide unique, efficient sectionalising solutions to reduce outage durations.

Designed for the toughest conditions

Junction bars are fully shielded, submersible and resistant to harsh materials.
Specifications
200 A loadbreak connector ratings in accordance with IEEE Std 386 standard
Voltage ratings 15 kV
25 kV 35 kV
Standard voltage class
15 25 35
Maximum rating phase-to-phase
14.4
26.3 36.6
Maximum rating phase to-ground 8.3
15.2 21.1
AC 60 Hz 1-minute withstand
34
40 50
DC 15-minute withstand
53
78 103
BIL and full wave crest
95
125 150
Minimum corona voltage level
11
19 26
Current ratings
15 kV
25 kV 35 kV
Continuous
200 A rms
200 A rms 200 A rms
Switching
10 make/break operations at 200 A rms at 14.4 kV
10 make/break operations at 200 A rms at 26.3 kV 10 make/break operations at 200 A rms at 36.6 kV
Fault closure
10,000 A rms sym. at 14.4 kV for 0.17s after 10 switching operations
10,000 A rms sym. at 26.3 kV for 0.17s after 10 switching operations 10,000 A rms sym. at 36.6 kV for 0.17s after 10 switching operations
Short time
10,000 A rms sym. for 0.17s 
10,000 A rms sym. for 0.17s 10,000 A rms sym. for 0.17s 
3,500 A rms sym. for 3.0s
3,500 A rms sym. for 3.0s 3,500 A rms sym. for 3.0s
600 A deadbreak connector ratings in accordance with IEEE Std. 386 standard
Voltage ratings
15 kV
25 kV
35 kV
Standard voltage class
25
25
35
Maximum rating phase-to-ground
15.2
15.2
21.1
AC 60 Hz 1-minute withstand
40
40
50
DC 15-minute withstand
78
78
103
BIL and full wave crest
125
125
150
Minimum corona voltage level
19
19
26
Current ratings
15 k
25 kV
35 kV
600 A interface**
Continuous
600 A rms
600 A rms
600 A rms
24-hour overload
1,000 A rms
1,000 A rms
1,000 A rms
Short time
25,000 A rms sym. for 0.17 s
25,000 A rms sym. for 0.17 s
25,000 A rms sym. for 0.17 s
10,000 A rms sym. for 3.0 s
10,000 A rms sym. for 3.0 s
10,000 A rms sym. for 3.0 s
200 A interface on loadbreak reducing tap plug (LRTP)* 
Continuous
200 A rms
200 A rms
200 A rms
Switching 
10 make/break operations at 200 A rms at 14.4 kV
10 make/break operations at 200 A rms at 26.3 kV
10 make/break operations at 200 A rms at 36.6 kV
Fault closure
10,000 A rms sym. at 14.4 kV for 0.17s after 10 switching operations
10,000 A rms sym. at 26.3 kV for 0.17s after 10 switching operations
10,000 A rms sym. at 36.6 kV for 0.17s after 10 switching operations
Short time 
10,000 A rms sym. for 0.17 s
10,000 A rms sym. for 0.17 s
10,000 A rms sym. for 0.17 s
3,500 A rms sym. for 3.0s
3,500 A rms sym. for 3.0s
3,500 A rms sym. for 3.0s
*System design and protection must recognise the ratings of the 200 A interface
**Optional 900 A rating is available