Eaton’s Cooper Power series junction bars are designed for vault or apparatus applications and can be used for looping, tapping and sectionalising.
200 A loadbreak connector ratings in accordance with IEEE Std 386 standard |
|||
Voltage ratings | 15 kV |
25 kV | 35 kV |
Standard voltage class |
15 | 25 | 35 |
Maximum rating phase-to-phase |
14.4 |
26.3 | 36.6 |
Maximum rating phase to-ground | 8.3 |
15.2 | 21.1 |
AC 60 Hz 1-minute withstand |
34 |
40 | 50 |
DC 15-minute withstand |
53 |
78 | 103 |
BIL and full wave crest |
95 |
125 | 150 |
Minimum corona voltage level |
11 |
19 | 26 |
Current ratings |
15 kV |
25 kV | 35 kV |
Continuous |
200 A rms |
200 A rms | 200 A rms |
Switching |
10 make/break operations at 200 A rms at 14.4 kV |
10 make/break operations at 200 A rms at 26.3 kV | 10 make/break operations at 200 A rms at 36.6 kV |
Fault closure |
10,000 A rms sym. at 14.4 kV for 0.17s after 10 switching operations |
10,000 A rms sym. at 26.3 kV for 0.17s after 10 switching operations | 10,000 A rms sym. at 36.6 kV for 0.17s after 10 switching operations |
Short time |
10,000 A rms sym. for 0.17s |
10,000 A rms sym. for 0.17s | 10,000 A rms sym. for 0.17s |
3,500 A rms sym. for 3.0s |
3,500 A rms sym. for 3.0s | 3,500 A rms sym. for 3.0s |
600 A deadbreak connector ratings in accordance with IEEE Std. 386 standard |
|||
Voltage ratings |
15 kV |
25 kV |
35 kV |
Standard voltage class |
25 |
25 |
35 |
Maximum rating phase-to-ground |
15.2 |
15.2 |
21.1 |
AC 60 Hz 1-minute withstand |
40 |
40 |
50 |
DC 15-minute withstand |
78 |
78 |
103 |
BIL and full wave crest |
125 |
125 |
150 |
Minimum corona voltage level |
19 |
19 |
26 |
Current ratings |
15 k |
25 kV |
35 kV |
600 A interface** |
|||
Continuous |
600 A rms |
600 A rms |
600 A rms |
24-hour overload |
1,000 A rms |
1,000 A rms |
1,000 A rms |
Short time |
25,000 A rms sym. for 0.17 s |
25,000 A rms sym. for 0.17 s |
25,000 A rms sym. for 0.17 s |
10,000 A rms sym. for 3.0 s |
10,000 A rms sym. for 3.0 s |
10,000 A rms sym. for 3.0 s |
|
200 A interface on loadbreak reducing tap plug (LRTP)* |
|||
Continuous |
200 A rms |
200 A rms |
200 A rms |
Switching |
10 make/break operations at 200 A rms at 14.4 kV |
10 make/break operations at 200 A rms at 26.3 kV |
10 make/break operations at 200 A rms at 36.6 kV |
Fault closure |
10,000 A rms sym. at 14.4 kV for 0.17s after 10 switching operations |
10,000 A rms sym. at 26.3 kV for 0.17s after 10 switching operations |
10,000 A rms sym. at 36.6 kV for 0.17s after 10 switching operations |
Short time |
10,000 A rms sym. for 0.17 s |
10,000 A rms sym. for 0.17 s |
10,000 A rms sym. for 0.17 s |
3,500 A rms sym. for 3.0s |
3,500 A rms sym. for 3.0s |
3,500 A rms sym. for 3.0s |
|
*System design and protection must recognise the ratings of the 200 A interface |
|||
**Optional 900 A rating is available |