Eaton's Cooper Power series NOVA-TS triple-single recloser system allows multi-mode configuration for coordinated, precise automation. The system includes three single-phase NOVA-TS reclosers, each with its own manual trip lever and mechanical contact position indicator; one Form 6 triple-single (TS) recloser control; and one compatible, common junction box, including three interconnecting cables to the NOVA-TS reclosers and one receptacle to provide easy access to the Form 6-TS control cable.
15-8-400 |
15-12-630 |
15-12-800 |
27-8-400 |
27-12-630 |
27-12-800 |
38-8-400 |
38-12-630 |
38-12-800 |
||
Maximum design voltage (kV) |
15.5 | 15.5 | 15.5 | 27.0 | 27.0 | 27.0 | 38.0 | 38.0 | 38.0 | |
Nominal operating voltage (kV) |
14.4 | 14.4 | 14.4 | 24.9 | 24.9 | 24.9 | 34.5 | 34.5 | 34.5 | |
Basic Insulation Level (BIL**) (kV) |
110 | 110 | 110 | 125 | 125 | 125 | 170 | 170 | 170 | |
60 Hertz withstand voltage (kV) |
Dry, one minute |
50 | 50 | 50 | 60 | 60 | 60 | 70 | 70 | 70 |
Wet, ten seconds |
45 | 45 | 45 | 50 | 50 | 50 | 60 | 60 | 60 | |
Max RIV at 1.0 MHz |
9.4 kV (µV) |
100 | 100 | 100 | – |
– |
– |
– |
– |
– |
16.4 kV (µV) |
– |
– |
– |
100 | 100 | 100 | – |
– |
– |
|
23.0 kV (µV) |
– |
– |
– |
– |
– |
– |
100 | 100 | 100 | |
Continuous current ratings (A) |
400 | 630 | 800 | 400 | 630 | 800 | 400 | 630 | 800 | |
Symmetrical interrupting current (A) |
8000 | 12500* | 12500* | 8000 | 12500* | 12500* | 8000 | 12500 | 12500 | |
Overload capability |
125% - 8 Hours (A) |
500 | 788 | None | 500 | 788 | None | 500 | 788 | None |
150% - 4 Hours (A) |
600 | 945 | – |
600 | 945 | – |
600 | 945 | – |
|
Cable charging current (A) |
10 | 10 | 10 | 25 | 25 | 25 | 40 | 40 | 40 | |
Line charging current (A) |
2 | 2 | 2 | 5 | 5 | 5 | 5 | 5 | 5 | |
Three-second current, Sym. (A) |
8000 | 12500* | 12500* | 8000 | 12500* | 12500* | 8000 | 12500 | 12500 | |
Minimum mechanical/electrical operations without maintenance (C-O) 10,000 | ||||||||||
* 16.0 kA option is also available (Making Current is 40 kA Asymmetrical Peak) |
||||||||||
**Extended BIL option available on 15.5 kV and 27 kV products |
Percent of maximum circuit interrupting rating |
Minimum X/R ratio |
Number of unit operations at 12.5 kA |
Number of unit operations at 16.0 kA |
15-20 | 4 | 88 | 44 |
45-55 | 8 | 112 | 56 |
90-100 | 17 | 32 | 16 |
Total 232 | Total 116 |
Visit this page for information on earlier models.
Eaton customers can access software, firmware and additional product documentation at My.Eaton.com. To request access, visit My.Eaton.com and complete the registration form. Please note that requests for access can take several days to process. If your matter is urgent, contact the customer support group at 866-975-7347.
In the wake of a storm or disaster, Eaton understands that safety and speed of response is everything. You can rely on Eaton Care teams to plan, protect and connect.