Eaton's Cooper Power series VSO recloser features three vacuum interrupters, oil insulation and an operating mechanism in an integral mounting frame. The electronic control is housed in a separate cabinet. Constructed of welded angle and channel steel, the VSO recloser frame facilitates recloser handling, simplifies mounting procedures and adds rigidity to the mounting structure. It provides a convenient mounting location for the tank-lifting windlass, which allows easy access to the interior of the recloser whether it is mounted on the pole or in the substation.
Nominal system voltage (kV rms) |
34.5 | |
Rated maximum voltage (kV rms) |
38 | |
Rated impulse withstand voltage BIL) (kV crest) |
150 | |
60 Hz withstand voltage (kV rms) |
dry, one minute |
70 |
wet, 10 seconds |
60 | |
Maximum Radio influence |
@ 23 kV (uV) |
100 |
Maximum continuous current (amps) |
560* | |
Interrupting current (rms sym. amps) |
VSO 12 |
12000 |
VSO 16 |
16000 | |
Three-second current, symmetric, A |
VSO 12 |
12000 |
VSO 16 |
16000 | |
Momentary current, asymmetric, A | VSO 12 | 20000 |
VSO 16 | 25600 | |
Cable charging current, A | 5 | |
Magnetising current, A | 19.6 | |
*An 800 A accessory is available |
Percent of maximum circuit interrupting rating |
Maximum X/R ratio |
Number of unit operations |
15-20 | 4 | 88 |
45-55 | 8 | 112 |
90-100 | 16 | 32 |
Total 232 |
Volts |
Inductive ac (amps) |
Non-inductive Ac (amps) |
Inductive dc (amps) |
Non-inductive dc (amps) |
24 | – |
– |
15.0 | 20.0 |
48 | – |
– |
7.5 | 10.0 |
120 | 60 | 80 |
– |
– |
125 | – |
– |
1.5 | 2.0 |
240 | 30 | 60 | – |
– |
250 | – |
– |
0.45 | 0.5 |
Trip solenoid | Operating voltage, Vdc | 24 | |
Peak current, A | 10.7 | ||
Actuation time, cycles | 1 | ||
Close solenoid | Operating voltage, Vdc | 24 | |
Peak current, A | 10.8 | ||
Actuation time, cycles | 2.75 | ||
Standard |
Accessory |
||
Spring charging motor | Operating voltage, Vac |
240 | 120 |
Voltage range, Vac |
160-257 | 90-127 | |
Maximum current, RMS, A |
12.9 | 18 | |
Steady state current, A |
4.1 | 9 | |
Motor running time, cycles |
40 | 40 | |
Sensing current transformers | 1000:1 | ||
Maximum arcing time, cycles |
1.0 | ||
Interrupting time, cycles |
2.5 |
Operating temperature, °C |
Minimum |
-30 |
Maximum |
+50 |
|
Closing mechanism | Spring operated | |
Opening mechanism |
Spring operated |
|
Contact gap, mm (in) |
13 (.5) | |
Close contact travel time, cycles |
.75 | |
Open contact travel time, cycles |
.5 | |
Allowable contact erosion, mm (in) |
3 (.125) | |
Opening time, 24 Vdc solenoid, Signal to contact part, msec |
25 | |
Closing time, 24 Vdc solenoid, Signal to contact make, msec |
50 | |
Mechanical life open-close, no load, operations |
2500 |
Visit this page for information on earlier models.
Eaton customers can access software, firmware and additional product documentation at My.Eaton.com. To request access, visit My.Eaton.com and complete the registration form. Please note that requests for access can take several days to process. If your matter is urgent, contact the customer support group at 866-975-7347.
In the wake of a storm or disaster, Eaton understands that safety and speed of response is everything. You can rely on Eaton Care teams to plan, protect and connect.