Power factor correction capacitors

AutoVAR 300

The Eaton AutoVAR 300 is designed for low-voltage applications with a variable system load where maintaining a precise target power factor is required. With a heavy-duty, three-phase capacitor construction in a small, wall-mount footprint, this product is ideal for applications with little space to spare. TEST

Remotely control banks of contactor-connected capacitors

A door-mounted microprocessor controller with optional communication capabilities via a Modbus RS-485 (additional communication protocols supported via Eaton PXG900) allows users to remotely control the capacitors connected to the AutoVAR 300.

Easily meet power factor target values

The load is monitored so that the AutoVAR 300 can automatically bring individual capacitors in and out as required to meet the necessary power factor.
Specifications

AutoVAR 300 capacitor product specifications

Operating temperature

-20°C to +46°C

Storage temperature

-40°C to +55°C

Cabinet assembly certifications

UL 508A

CSA C22.2 no 190

Capacitor certifications UL 810

Wall-mounted AutoVAR 300 switched capacitor banks – low-voltage applications

Catalogue number kVAR Step x kVAR Rated current amperes

Base delivery weight

Lbs (kg)

240 V
25MCSR2313 25 5 x 5 60 217 (98.5)
50MCSR2313 50 5 x 10 120 255 (155.8)
75MCSR2313 75 5 x 15 180 260 (118.0)
100MCSR231 100 5 x 20 240 270 (122.6)
125MCSR231 125 5 x 25 300 292 (132.6)
480 V
50MCSR4313 50 5 x 10 60 200 (90.8)
75MCSR4313 75 5 x 15 90 210 (95.3)
100MCSR4313 100 5 x 20 120 210 (95.3)
125MCSR4313 125 5 x 25 150 240 (109.0)
150MCSR4313 150 5 x 30 180 240 (109.0)
175MCSR4313 175 5 x 35 210 260 (118.0)
200MCSR4313 200 5 x 40 241 270 (122.6)
225MCSR4313 225 5 x 45 270 290 (131.7)
250MCSR4313 250 5 x 50 300 292 (132.6)
600 V
50MCSR6313 50 5 x 10 48 200 (90.8)
75MCSR6313 75 5 x 15 72 210 (95.3)
100MCSR6313 100 5 x 20 96 210 (95.3)
125MCSR6313 125 5 x 25 120 240 (109.0)
150MCSR6313 150 5 x 30 144 240 (109.0)
175MCSR631 175 5 x 35 168 260 (118.0)
200MCSR631 200 5 x 40 192 270 (122.6)
225MCSR631 225 5 x 45 216 290 (131.7)
250MCSR631 250 5 x 50 240 292 (132.6)

Spare fuses

Fuse part number 240 Volts 480 Volts 600 Volts Amperes
SP030217-0029J 5 10 10 30
SP030217-0037D --- 15 20 50
SP030217-0037E 10 20 --- 60
SP030217-0037G --- 25 25–30 80
SP030217-0037J 15 30 40 100
SP030217-0037K 20 40 50 125
SP030217-0037L 25 50 --- 150

Options

Description Option code Additional weight added
Remote alarm relay terminal block – relay terminal block for a remote alarm to indicate controller alarm status A 1lb (0.4kg)
Communicating controller (Modbus RS-485) C 1lb (0.4kg)
Hand-off-auto switch – provides manual control to connect or disconnect capacitor stages, regardless of controller output  H 5lbs (2.2kg)
Moulded case circuit breaker M 50lbs (22.6kg) enclosure weight added plus circuit breaker weight
Weather-resistant enclosure (NEMA 3R gasketed) W 10lbs (4.5kg)

AutoVAR 300 integrated main breakers

kVAR AutoVAR rated current amperes

Breaker size

(amperes)

Breaker interrupting rating

(kA)

Breaker weight

Lbs (kg)

Standard wire lug size
240 V
25 60 125 100 10 (4.5) (1) #3–350
50 120 250 100 10 (4.5) (1) #3–350
75 180 250 100 10 (4.5) (1) #3–350
100 240 400 100 10 (4.5) (2) #3/0–250
125 300 600 100 25 (11.4) (2) #3/0–350
480 V
50 60 125 65 10 (4.5) (1) #3–350)
75 90 125 65 10 (4.5) (1) #3–350)
100 120 250 65 10 (4.5) (1) #3–350)
125 150 250 65 10 (4.5) (1) #3–350)
150 180 250 65 10 (4.5) (1) #3–350)
175 210 400 65 10 (4.5) (2) #3/0–250
200 240 400 65 10 (4.5) (2) #3/0–250
225 270 400 65 10 (4.5) (2) #3/0–250
250 300 600 65 25 (11.4) (2) #3/0–350
600 V
50 48 125 35 10 (4.5) (1) #3–350
75 72 125 35 10 (4.5) (1) #3–350
100 96 250 35 10 (4.5) (1) #3–350
125 120 250 35 10 (4.5) (1) #3–350
150 144 250 35 10 (4.5) (1) #3–350
175 168 250 35 10 (4.5) (1) #3–350
200 192 400 35 10 (4.5) (2) #3/0–350
225 216 400 35 10 (4.5) (2) #3/0–350
250 240 400 35 10 (4.5) (2) #3/0–350