Download document () of 20
Surge protection

MTL MA3100 Type 2 surge protector

The Crouse-Hinds series MTL MA3100 surge protectors are used for applications described by IEC 61312 where the surge protector could carry a partial share of the lightning surge current. The Class I devices, rated for 50kA (10/350µs), are deployed at the service entrance, followed by Class II rated devices at key power panels. Sensitive systems can then be locally protected by a Class III surge protector (such as an MTL MA15).

Safety
High nominal discharge rating of 20kA
Installation ease
Space-saving design, DIN-rail mounting
Reliability
IEC Class I, II and III products available

Certification and compliance

  • IEC 61643-11:2011-03
  • UL1449 3rd Edition
  • IP20
  • Flammability rating according to UL94: VO

Design features

  • Space-saving design, DIN rail mounting
  • Full range of AC mains power applications
  • Coordinated surge protection to IEC 61312; rated according to IEC 61643
  • UL1449 3rd Edition, Type 4 Recognised Component, VZCA2 and VZCA8, File E315539
  • 200kA short-circuit current rating
  • IEC Class I, II and III products available
  • Single pole peak of 50kA (10/350µs) for Class I devices
  • Multiple pole peak of >100kA (10/350µs) for Class I devices
Specifications

Ordering information

For ordering information, please use the link below to visit the resources section for this product family and look under "Catalogues".