Download document () of 20
Medium-voltage transformers

PEAK three-phase pad-mounted transformer

Eaton's Cooper Power series PEAK three-phase pad-mounted transformer is filled with FR3 dielectric fluid and is uniquely designed to manage increased loads and temporary overload capacity without loss of life expectancy compared to mineral oil-filled alternatives. Offering the ability to operate beyond full rated load from 12% to 22%, the transformer’s smaller, lighter footprint further enhances value.

Base rating
45-12,000 kVA
Available slash ratings
65/75 °C (12% kVA increase); 55/75 °C (22% kVA increase)
75 °C average winding rise
Lower cost, more compact design

Core features

  • Designed to improve performance in terms of kVA rating, compact dimensions, lighter weight, safety and sustainability
  • Offers increased temporary overload capacity without loss of life expectancy (with 55/75 or 65/75 °C slash rating)
  • Utilizing an advanced high-temperature insulation system approach and an optimized core and coil design, a 75 rise PEAK transformer results in a smaller footprint and a lighter unit capable of the same ratings as a physically larger 65 °C AWR rated unit

Better manage temporary overloads

Eaton's Cooper Power series PEAK three-phase pad-mounted transformers can be loaded beyond base-rated load up to 122% of base kVA, helping utilities to more precisely size transformers based on periods of peak demand — without impacting insulation life.

Increased transformer reliability and lifespan

The capacity to load PEAK transformers continuously at higher temperature and varying loads without causing damage to the transformer enhances overall system reliability while providing a longer equipment lifespan (conforms to IEEE standard C57.154).

Just as much power in smaller design

A 75 °C Average Winding Rise (AWR) PEAK transformer results in a smaller footprint and a lighter unit capable of the same ratings as a physically larger 65 °C AWR rated unit.
Specifications

Ratings

Base kVA at 75 AWR
45 kVA to 12,000 kVA
kVA increase at 65/75 AWR
+12% (max rating up to 13,440 kVA)
kVA increase at 55/75 AWR
+22% (max rating up to 14,640 kVA)
Primary voltage
2400 V to 46,000 V
Secondary voltage
120 V to 14,400 V
Basic Impulse Level (BIL)
30 kV to 250 kV
Additional forced-air ratings
+15%, +25%, +33% to base kVA

Standards

ANSI/IEEE
C57.154, C57.12.00 and C57.12.34
CSA
C227.4 
NEMA (sound level)
NEMA TR-1
Third-party approval/recognition
FM Global (Indoor & Outdoor), UL/cUL – available for most ratings

Enclosure

Layout
Compartmental type
Tamper resistance
Three-point latching and padlock system with recessed penta-head bolts
Enclosure integrity
Meets or exceeds ANSI/IEEE C57.12.28 and C57.12.29 (if stainless constructioni)
Material 
Mild or stainless steel (304L)
Enclosure environment
Outdoor
Insulating medium 
Air

Key features

Distribution transformer
Three-phase pad-mounted
Install location
Outdoor
Power direction
Step-down and step-up
Download Links