Knowledge Search
Download document () of 20

CEAG eXlink Hazardous Area Hot Swap Connectors

Crouse-Hinds series CEAG eXlink plugs, inlets, receptacles and connectors are designed for hot swapping (connecting and disconnecting) of apparatus in Zones 1 and 2 hazardous areas without disconnecting terminals or shutting down circuits, and without a hot work permit.

Available in polyamide, nickel-plated brass and stainless steel, eXlink hot swap connectors allow for the assembly, maintenance and repair of electrical equipment to be handled simply, safely and at a low cost.

Certifications and compliances

eXlink 4-pole / 4-pole + PE

  • Marking accd. to 94/9/EC: Ex II 2 G Ex de IIC T6 / Ex II 2 G Ex ia/ib IIC T6; Ex II 2 D tD A21 IP66 T80°C
  • EC-Type Examination Certificate: PTB 03 ATEX 1016 X
  • IECEx Certificate of Conformity: IECEx BKI 06.0005X
  • Marking accd. to IECEx: Ex de IIC T6 / Ex ia/ib IIC T6; Ex tD A21 IP66 T80°C
  • Permissible ambient temperature: -55°C to +40°C (rated current 10A); -55°C to +75°C (rated current 2A); -20°C to +40°C (elbow, plastic)
  • Protection class acc. EN 60598: II (plastic); I (metal)
  • Degree of protection accd. to EN 60529: IP66/IP68 (with closed and locked protective caps or duly plugged and locked components)

eXlink 6+1-pole / 7-pole

  • Marking accd. to 94/9/EC: Ex II 2 G Ex de IIC T6 Ex ia/ib IIC T6; Ex II 3 D Ex tc IIIC T80°C DC
  • EC-Type Examination Certificate: PTB 06 ATEX 1031 X
  • EC-Declaration of Conformity: CCH 13 ATEX 1010 X
  • IECEx Certificate of Conformity: IECEx BKI 06.0005X
  • Marking accd. to IECEx: Ex ed IIC T6 / Ex ia/ib IIC T6
  • Permissible ambient temperature: -20°C to +40°C (rated current 16A)
  • Protection class acc. to EN 60598: II (plastic); I (metal)
  • Degree of protection accd. to EN 60529: IP66/IP68 (with closed and locked protective caps or duly plugged and locked components)

eXlink mining

  • Marking accd. to 94/9/EC: Ex I M2 Ex de I
  • Type of protection: Ex de IIC T6
  • EC-Type Examination Certificate: BVS 07 ATEX E 020 X
  • Degree of protection accd. to EN 60529: IP66/IP68 with closed and locked protective caps or duly plugged and locked components

Design features

eXlink 4-pole and 6-pole

  • Hot swap
  • Standard IP protection: IP66/IP68
  • Permissible ambient temperature from -55°C to +70°C
  • Up to 250V 10A (4-pole); up to 400V 16A (6-pole)
  • Stainless steel or nickel-plated brass enclosures for highest mechanical protection
  • Max. 4-pole + PE connections (4-pole); max. 7-pole (6-pole + PE) connections (6-pole)
  • Mining (EX I M2) certified
  • Well-known and reliable bonding technique (crimp connection); a screw-less technique (cage clamp) can be used for selected types
  • A special plug and connector for the use of armored cable is available
  • Receptacle and inlet are equipped with metric or NPT thread to screw directly into electrical apparatus; the factory potted metal versions can be used directly into Ex-d enclosures without additional certification to be applied

eXlink mining

  • Quick connection and disconnection in areas where there is a risk of fire damp
  • Secure electrical and mechanical connection in compact housings
  • No switching off and disconnection necessary
  • Reduction in downtimes
  • Maximum ingress protection: IP66/IP68
  • Wide operating temperature range
  • Infinite flexibility due to different versions and codings
  • Reverse polarity protected connections by coding

Standard materials

  • Plug, coupler, inlet < 2000 cm3 and flange socket – polyamide, nickel-plated brass or 316L stainless steel
  • Inlet > 2000 cm3 and plug/coupler for armored cables – nickel-plated brass or 316L stainless steel

eXlink mining

  • Enclosure – 316L stainless steel
Specifications

Ordering information

For ordering information, please use the link below to visit the resources page for this product family and look under the "Catalogs" heading.