The explosion-protected linear luminaires are approved for areas with gas explosion-hazard zones 1 and 21 as well as dust explosion-hazard zones 21 and 22, according to the APEX 94/9/EG directive. With a high IP66 protection rating and a robust housing they are ideal for use in industrial environments. The completely monitored linear luminaires are equipped with energy-saving dual-channel LED moduls. The power saving observe luminescent screen tubes represent 20%.
Order code | Description |
12265516103 | eLLK 92 LED 400A V-CG-S 2 x M25, plastic gland |
12265516111 | eLLK 92 LED 400A V-CG-S 4 x M20, metal thread |
12266516103 | eLLK 92 LED 800A V-CG-S 2 x M25, plastic gland |
12266516111 | eLLK 92 LED 800A V-CG-S 4 x M20, metal thread |
Marking acc. to 94/9/EG | II 2G Ex de mb II T4 Gb II 2D Ex tb IIIC T80 °C Db IP66 |
EC-Type Examination Certificate: | BVS 09 ATEX E 034 |
IECEx-inspection certificate: | IECEX BVS 09.0033 |
Marking acc. to IECEx: | Ex db eb mb op is IIC T4 Gb Ex tb IIIC T80 °C Db |
Housing material: | Glass fibre reinforced polyester |
Protective bowl: | Polycarbonate |
Rated voltage: | AC: 220 – 254 V DC: 195 – 250 V |
Circuit: | EVG / CG-S |
Rated current: | 0.15 A / 0.08 A (eLLK 92 LED 400A V-CG-S) 0.25 A / 0.13 A (eLLK 92 LED 800A V-CG-S) |
Power consumption: | 29 W (eLLK 92 LED 400A V-CG-S) 57 W (eLLK 92 LED 800A V-CG-S) |
Power factor cos: | ≥ 0.95 |
Permissible temperature range: | –25 °C up to + 50 °C |
Cable infeeds: | Ex-e-cable glands M25 x 1.5 (plastic) for cables Ø 8 - 17 mm, Option: M20 x 1.5 metal thread* |
Connection terminals: | L1, L2, L3, L, N, PE; max. 2 x 6 mm2 per terminal |
Light source: | LED module 400A - 2 x 13 W LED module 800A - 2 x 26 W |
Weight: | 7.4 kg (eLLK 92 LED 400A V-CG-S) 11.1 kg (eLLK 92 LED 800A V-CG-S) |
*With dust cover for unlocked entering/metal thread |