Búsqueda de conocimientos
Descargar documento () de 20

Ampgard medium-voltage motor control (2.5, 5.0, 7.2 kV)

Ampgard medium-voltage starters are the premier solution in motor control, performance, reliability and protection. Eaton offers a complete line of full voltage and reduced voltage starter types. This broad selection of medium-voltage control supports a wide range of industrial applications including pulp and paper, water and wastewater, oil and gas and HVAC.

Voltage Class
7.2 kV
Horsepower
up to 8000 Hp
Main Bus Rating
up to 3000 A

Características Principales

  • Designed and tested to meet UL 347
  • Available with arc-resistant enclosures that comply with IEEE Standard C37.20.7-2017
  • Outfitted with Eaton’s Type SL vacuum contactors - the industry’s highest interrupting ratings
  • Proven durability with a long-life isolation switch rated for 10,000 mechanical operations
  • Top-mounted main bus for convenient installation and maintenance
  • Starter types include full voltage non-reversing (FVNR), reduced voltage reactor (RVR), reduced voltage autotransformer (RVAT) and reduced voltage solid state soft starter (RVSS)
  • Available with Eaton EMR series of motor protection relays for comprehensive and safe motor monitoring and starting control   
  • Completely front accessible
  • Two-high 400 A and one-high 800 A starter configurations

Ampgard, the name motor applications rely on

Eaton has been an industry leader for more than 50 years, providing UL 347 certified medium-voltage control. When it comes to controlling and protecting medium-voltage motors, the Ampgard family is the premier high-performance choice.

Money saving double-bus design

When close-coupling Ampgard starters with medium-voltage drives for synchronous transfer applications the double bus eliminates external cables and associated accessories required to connect motor-select and bypass starters. Material and labor savings can be upwards of $25,000 for a four-motor system.

Remote operator for enhanced safety

The Ampgard Remote Operator (ARO) for the starter isolation switch that, when mounted on the front of the starter allows personnel to safely open and close the switch from outside the arc flash boundary.

Los balastos integrados agilizan las líneas de producción multiconfiguración

Solución compacta y económica que combina el interruptor principal y los arrancadores de motor Ampgard de Eaton con la unidad de media tensión SC9000 a través de un bus común en un solo ensamblaje integrado de alta calidad. Todo el conjunto está disponible como resistente a arcos eléctricos.
Especificaciones

Ratings

POWER RATING 50-5000 Hp
INPUT VOLTAGE RATING 2400-6900 V
BASIC IMPULSE LEVEL (BIL) 60 kV BIL
INTERRUPTING RATING 50 kA rms symmetrical
AMBIENT TEMPERATURE 0 to 40 degrees C

Standards

UL                                                                                        347
NEMA ICS3
CSA C22.2
THIRD PARTY RECOGNITION/APPROVAL UL/cUL available for most configurations
SEISMIC QUALIFICATION IBC

Enclosure

ENCLOSURE TYPE                                                                                         
NEMA 1, NEMA 12, NEMA 3R
ACCESSIBILITY
Front                                                                  
INDOOR SECTION DIMENSIONS (TYPICAL)
36"w x 30"d x 92"h
BUS INSULATION Uninsulated is standard, heat shrink sleeve is optional
BUS SUPPORTS Glass polyester

DEVICES

SWITCHING DEVICE                                           
Vacuum contactor (400A / 800A)
CONTACTOR CONNECTION
Bolted is standard, stab is optional
FUSE MOUNTING Bolted is standard, stab is optional
Descargar enlaces