Télécharger le document () de 20
Disjoncteurs

PF6/7 xPole Residual Current Circuit Breaker

With the PF6 and PF7 xPole RCCBs, Eaton offers a complete range of compact residual current devices for fault current/residual current and additional protection, suitable for residential and small commercial use.

Rated short circuit strength
6 kA or 10 kA
according to
IEC/EN 61008
Sensitivity
AC and pulsating DC

Caractéristiques principales

  • Twin-purpose terminal (lift/open-mouthed) above and below
  • Busbar positioning optionally above or below
  • Free terminal space despite installed busbar
  • Universal tripping signal switch, also suitable for PL., PFL., Z-A. can be mounted subsequently
  • Auxiliary switch Z-HK can be mounted subsequently
  • Contact position indicator red - green
  • Delayed types suitable for used with standard fluorescent lamps, with or without electronic ballast (30mA-RCD: 30 units per phase conductor, 100mA-RCD: 90 units per phase conductor)

PF7 

  • A complete spectrum of compact residual current devices for a wide range of applications to 100 A
  • Rated short circuit strength 10 kA
  • Especially for protection against accidents caused by current and property protection
  • Wide variety of types (G, S, A, G/A, S/A, R, U, ...)
  • Special type U for frequency converter applications with high surge current proof
  • Comprehensive range of accessories can be mounted subsequently
  • Shape compatible with and suitable for standard busbar connection to other devices of the P-series

PF6

  • Economy series of RCD
  • Rated short circuit strength 6 kA
  • For fault current/residual current protection and additional protection
  • Comprehensive range of accessories can be mounted subsequently

 

 

 

Different types for various applications. . .

Type -A:
Protects against special forms of residual pulsating DC which have not been smoothed.
 

 

PF4/6/7 xPole Residual Current Circuit Breaker

Type -S:
Selective residual current device sensitive to AC, type -S. Compulsory for systems with surge arresters downstream of the RCD.

 

Type -G:
High reliability against unwanted tripping. Compulsory for any circuit where personal injury or damage to property may occur in case of unwanted tripping.

 

PF4/6/7 xPole Residual Current Circuit Breaker
Type -S/A:
Additionally protects against special forms of residual pulsating DC which have not been smoothed.

Type -G/A:
Additionally protects against special forms of residual pulsating DC which have not been smoothed. Special types for X-ray application PFIM-...-R.

 

PF4/6/7 xPole Residual Current Circuit Breaker

Reliable protection for machines

These products provide an optimal system and additional protection against residual earth leakage currents for a wide range of applications by offering different tripping characteristics to cater for various electrical systems and components that can generate. Available in a comprehensive range of nominal current values and with optional accessories.

The PF6 and PF7 are suitable for protection

The tripping of the PF6 and PF7 xPole RCCBs are line voltage-independent. Consequently, the RCCB is suitable for “fault current/residual current protection” and “additional protection” within the the meaning of the applicable installation rules.
Spécifications
Mettre en évidence les différences
Afficher uniquement les différences
Masquer les champs vides
Liens de téléchargement