This product has been discontinued and is no longer available. For technical support contact FireTechSupport@Eaton.com.
The JSB FX4200 range are high specification conventional control panels designed for a wide variety of building types and sizes. Available in a choice of 2, 4 and 8 zone versions, the FX4200 range is designed for ease of installation and simple operation.
The FX4200 range are easy to use, with a simple “one-shot” test facility to ensure regular mandatory testing can be quickly and regularly accomplished. Other standard features, such as class change, zone or sounder circuit disabling and programmable relay output facilities complete a highly competitive solution.
Conventional 2 zone control panel | FX4202 |
Conventional 4 zone control panel | FX4204 |
Conventional 8 zone control panel | FX4208 |
Code |
FX4202 |
FX4204 |
FX4208 |
Description |
2 Zone control panel |
4 Zone control panel |
8 Zone control panel |
Standards |
EN54 Pt2 & Pt4 1998, EN50130 Pt4:1996, EN500081 Pt1:1992 & EN61000 Pt2:1994 |
EN54 Pt2 & Pt4 1998, EN50130 Pt4:1996, EN500081 Pt1:1992 & EN61000 Pt2:1994 |
EN54 Pt2 & Pt4 1998 |
Specification |
|||
Number of Zones |
2 |
4 |
8 |
Number of Detectors per Zone |
20 |
20 |
32 |
Number of Alarm Circuits |
2 |
2 |
2 |
Alarm circuit load |
150mA per circuit. 300mA total |
400mA per circuit. 800mA total |
400mA per circuit. 800mA total |
End of Line Devices |
Detection circuits: EOLM-1 monitoring unit. Alarm lines: 6.8K resistor |
Detection circuits: EOLM-1 monitoring unit. Alarm lines: 6.8K resistor |
Detection circuits: EOLM-1 monitoring unit. Alarm lines: 6.8K resistor |
Auxiliary Fire Signal/Fault Output |
Single pole changeover contacts ratings: 5A 24V dc |
Single pole changeover contacts ratings: 5A 24V dc |
Changeover contacts ratings: 5A 24V dc |
Auxiliary dc output |
24V dc fused. 30mA |
24V dc fused. 30mA |
24V dc fused. 30mA |
Mains Input Voltage |
230V ac +10%-15% |
230V ac +10%-15% |
230V ac +10%-15% |
Operating Voltage |
24V dc |
24V dc |
24V dc |
Standby Duration |
24 hours |
24 hours |
24 hours |
Battery |
1 x 12V 4Ah (sealed lead acid battery) |
1 x 12V 4Ah (sealed lead acid battery) |
1 x 12V 7Ah (sealed lead acid battery) |
Recharge Period |
24 hours |
24 hours |
24 hours |
Environmental |
|||
Operating Temperature |
-5°C to +40°C |
-5°C to +40°C |
-5°C to +45°C |
Humidity (non condensing) |
0 to 75% RH |
0 to 75% RH |
0 to 75% RH |
Physical |
|||
Construction |
ABS / Polycarbonate front and metal back box |
ABS / Polycarbonate front and metal back box |
ABS / Polycarbonate front and metal back box |
Dimensions (H x W x D) |
300mm x 300mm x 74mm |
300mm x 300mm x 74mm |
270mm x 395mm x 90mm |
Weight |
4.8kg |
4.8kg |
7kg |
Cable Entry |
Top: 10 x 20mm conduit entries Bottom: 1 x 20mm conduit entry (mains cable) Back: 1 x mains cable entry slot |
Top: 10 x 20mm conduit entries Bottom: 1 x 20mm conduit entry (mains cable) Back: 1 x mains cable entry slot |
Top: 18 x 20mm entries Back: cable entry aperture |
Support from Eaton