The DAU500 is all-in-one-box voice evacuation system. The wall mount panel contains a completely integrated voice evacuation system, capable of both standalone (for small systems) and network operation (for larger system expansion).
It is certified in accordance with EN54-16 and EN54-4, which are harmonized standards under Construction Products Regulation, mandatory in the European Union.
Powerful and flexible, DAU500 offers flexibility and optimisation for a range of voice applications large or small.
The DAU500 all-in-one public address and voice alarm system is designed to be flexible. Whether it's a tall building or large site you need to cover, ease of system extension and networking capabilities ensure that you can meet your project requirements, whilst you ensure your building occupants will hear the broadcast message when it matters most.
Expanding your voice alarm system
Expanding your DAU500 voice alarm system is easy. All that's needed is a multiplexer (EF-HEXAPOD6) that connects directly into a single/dual output line of the system. This will give you 6 speaker lines.
To extend the system further you can simply connect another 2 multiplexers to the same panel giving you 18 speaker lines that could cover 18 floors. (3 multiplexers per DAU500 panel is advised.)
Extending your voice system further
When it comes to much larger systems, where you need to extend your voice alarm system across a site for example, the DAU500 system's networking capabilities enable to you to easily do this by connecting DAU500 panels together.
The system allows you to connect up to 254 panels per network and, with this versatility, you can easily build your system today whilst planning for future system extension tomorrow.
The DAU500 voice alarm system range offers a variety of optional extras meaning that you can tailor the system to meet your needs.
Speakerline multiplexer (EF-HEXAPOD6)
With its 6 outputs, the DIN-rail mounted EF-HEXAPOD6 expands the number of loudspeaker lines on the DAU500 Public Address and Voice Alarm System, with a maximum of 6 lines per multiplexer, with up to 3 multiplexers per panel advised.
Fiber optic interface module (EF-FSC-MM)
This DIN-rail mounted, optical multimode fiber signal adapter interconnects system panels. It extends a single link range up to 2km and features a standard SC connector for the fiber cable, providing easy plug and play connectivity.
Programmable Input/Output module (EF-GPIO-16WAY)
This DIN-rail mounted I/O interface features programmable 16 input/16 output pins. It can trigger any user defined event to any zone/set of zones in the entire system, and transmit audio signal from built-in local audio input to any zone over system network.
End of line module
(EF-EOL-TL)
This IP33 protection rated end of line module enables selectable speaker load settings for the DAU500 system, that being 10%, 50% or 100% of the distributed amplifier unit's rated power.
Terminal box (EF-HTB / EF-HTB-W)
The terminal box is used to mount DAU500 DIN rail mountable peripherals such as the EF-HEXAPOD6 and the EF-GPIO-16WAY. It enables field termination to loudspeaker cables and, as a central termination point, makes service and maintenance easy.
The DAU500 voice alarm system is available with a variety of optional components and accessories. This means that you can easily tailor the system to meet the requirements of your current and future projects, whether the system you need is for a single building, across a site, either centralised or distributed.
DAU500 wall mount voice alarm system | EFDAU500 |
Accessories: | |
Speaker line multiplexer | EF-HEXAPOD6 |
16 way Input/Output module | EF-GPIO-16WAY |
Multimode fiber module | EF-FSC-MM |
End of line module - 10 pack | EF-EOL-TL |
Replacement fire microphone | EF-FMP |
1 x 100v Transformer standard | EF-T100 |
1 x 70v Transformer switchable | EF-T107 |
Terminal box | EF-HTB |
Terminal box with window | EF-HTB-W |
Number of zones | max. 6 local zones |
Maximum total loudspeaker load | 600 W RMS (420W RMS pure sinewave according to EN54-16) |
Power amplifiers | 6 x 100 W, modular (2 channels per module), bridgeable up to 3 x 200 W. Note: Line voltage dependant upon transformer used. |
Standby power amplifiers | 2 x 100 W / 1 x 200 W dedicated backup amplifiers |
Loudspeaker line monitoring | |
Built-in | 20 kHz AC monitoring with EOL module, short/open/impedance deviation |
Loudspeaker type | with 70 V/100 V step-down transformer |
Voice messages | |
Storage | max. 22 audio files x 5 minutes each, micro-SD card with content monitoring |
Message player | max. 2 simultaneous local message playback |
Controls and indications | |
General controls / indications | Lamp test button, silence button, power, evac, general fault LED indicators |
Fault indications | Power supply, system fault, network, zone fault |
Zone controls / indications | 6 x configurable zone selection button, zone EVAC/FAULT/BUSY LED indicators |
Evac manual control | EVAC message, ALERT message, SILENCE, RESET, fireman mic with PTT button |
Fireman microphone | Integrated Fireman Mic with priority and electrical monitoring |
Power supply equipment | Built-in power supply system, EN 54-4 certified. |
AC supply | 110 – 230 V AC, 50/60Hz |
AC current consumption | max. 5.3A @115 V AC / 2.65 A @230V AC |
Inrush current | 20 A @115 V AC, 40 A @230 V AC |
Power supply protection | Overload current limiting, over voltage shutdown, over temperature shutdown. |
Battery requirements | |
Type | Sealed, rechargeable lead-acid battery for stationary use |
Capacity | 10 – 55 Ah |
Charging time (80% capacity) | < 24 h |
Rated voltage | 24 V DC (2 x 12V) |
Battery dimensions | 2 batteries, each of max. 230 x 138 x 207 mm (LxWxH) (not supplied) |
Battery weight | max. total 32.6 kg |
Inputs | |
2 x BGM | 2 x independent balanced analogue in, line-level mono, 22 kΩ input impedance |
6 x EVAC in, 1 x SILENCE in, 1 x RESET in | monitored logic inputs, 4.7 kΩ + 10 kΩ EOL resistors |
8 x GPI | unmonitored logic inputs (pull-down, configurable active low/hi) |
Outputs | |
EVAC out, FAULT out | Potential-free relay output (configurable NO/NC) |
GPO | 8 x Open collector output (configurable NO/NC) max. max 24 vDC/110mA |
Loudspeaker out | 6 x 100 V transformer output, 20 kHz AC monitoring with EOL |
Amplifiers | |
Type | Class D |
Protection | over load shut down, over temperature shut down |
Backup amplifiers | 2 dedicated backup channels, auto backup at end stage failure, auto restore |
Efficiency | 80% @ rated power |
Output voltage | max. 100 V RMS or 70 V RMS (according to transformer setting) |
Rated power | max 100 W per channel |
Output bandwidth | 50 Hz – 20 kHz |
SNR | >80 dB |
THD + N | 0.1% @ rated power |
Networking | |
Max. number of devices in the network | 254 |
Max. number of zones | 254 |
Max. total system output power | 152 kW |
Number of simultaneous network audio | 2 |
Network audio transmission latency | 0.3 ms per device |
Local network | |
Architecture | Master-slave, up to 16 slave devices per DAU500 main unit |
Connection | 3 x L-Net port, RJ-45, powered daisy chain, digital audio & control data |
Cabling | X-over FTP CAT5e (or higher) |
Current consumption | max. 500 mA (up to 8 slave devices) per L-Net port |
Max. length of local bus: | |
default | 250 m |
Global network | |
Architecture | Peer-to-peer, up to 254 x DAU500 main units |
Connection | 2 x G-Net port, RJ-45, powered redundant ring, digital audio & control data |
Cabling | X-over FTP CAT5e (or higher) / multimode optical fiber |
Current consumption | max. 500 mA per port, reserved only for fiber extenders |
Max. distance between devices: | |
default | 250 m |
with fiber extenders | 2500 m (2km on fiber, 2 x 250m copper) |
Audio performance and mechanical details | |
Audio | |
Frequency response: | |
Local BGM | 50 Hz – 20 kHz |
Messages, network streaming | 100 Hz – 12 kHz |
Analog input- output latency | < 10 ms (stand-alone system) |
Network audio stream format | 24 kHz sampling, ADPCM compressed |
Message file input format | 24 kHz, 16 bit, mono WAV |
DSP features | HP/LP filter, multipoint parametric EQ |
Mechanical | |
Dimensions (HxWxD) | 80 x 52 x 28 cm |
Weight (full config, without batteries) | 29 kg |
Housing material | Steel / ABS |
IP rating | IP30 |
Mounting | Wall-mounted box |
Support from Eaton
Need product support?
Phone: 01753 608 700, option 3 then option 4