GuideLed SL is a safety lighting solution suited to most indoor applications according to EN 1838 such as escape route, anti-panic illumination and points of emphasis. The recessed version is the first choice for an unobtrusive, discreet appearance. It is easy to install thanks to a typical drill hole size of 68 mm. The surface-mounted version offers sufficient space for simple cable routing and connections.
Both versions have die-cast elements for optimum thermal management, enabling carefree operation in continuous mode, for example as a stand-by luminaire during the night.
The use of LEDs, LiFePo batteries, automatic testing and monitoring devices (CGLine+) significantly reduce the operating and maintenance costs of the installation.
New optics have been designed to efficiently illuminate linear escape routes and open spaces
The aim of emergency lighting is to enable people to exit a room or
building safely. It must also ensure that fire fighting and safety equipment can be easily found and operated when needed. This equipment includes (but is not limited to):
Lighting is required near each first aid kit, near each alarm and piece of fire fighting equipment, as well as each sign indicating a fire alarm system. In accordance with EN 1838, "near" generally means a distance of no greater than 2 metres, measured horizontally (this corresponds with distance a in the diagram below). The required level of illuminance on the equipment is 5 lx measured vertically – i.e. perpendicular to the usual horizontal illuminance measurements on one level. In comparison to the escape route requirement for 1 lx horizontally, different requirements apply in this situation for the light distribution from the safety luminaires, due to the flatter light angle of incidence.
GuideLed SL 13851.2 and 13852.2 CGLine+ meet the specific requirements of EN 1838
Your search "" did not match any documents or products.
Luminous flux at end of rated operating time | 100% @ 1h, 80% @ 2h, 55% @ 3h, 23% @ 8h |
Illumination in mains mode | 10% or 100% setting via switch, and possible additional levels adjustable via test button (30%, 70%, 100%) |
Operation | Maintained / Non-Maintained (via switched input L‘) |
Testing system | Automatic Test in compliance with EN 62034 Central monitoring via CGLine+ system |
Type of mounting | Surface or recessed mounting |
Housing material | Polycarbonate, aluminium heatsink |
Housing colour | White RAL 9016 |
Degree of protection | IP40 / IK03 (IP41 for recessed) |
Terminals | Through-wiring from mains (L, L’, N, PE) with up to 2.5 mm² CGLine+ bus through-wiring with up to 1.5 mm² |
Connection voltage | 220 - 240 V AC, 50/60 Hz |
Permissible ambient temperature range | 5°C to 45°C (NM), 0°C to 45°C (M), 35°C max. for 10 year lifetime |
Battery | LiFePO4 3.2 V / 3 Ah (Spare part: FT-BATLL3) |
Light source | 1 x 2 W LED, 4000 K, CRI ≥70, Lifespan 100 000h |