The detector features two parts: a transmitter-receiver and reflector. The transmitter-receiver directs a continuous infra-red beam towards the reflector which utilising a prism then sends back the beam to the transmitter-receiver which in turn registers the strength of the beam.
A fire or fault is signalled when the continuous beam is interfered between the two parts by smoke; reducing the strength of the beam. The transmitter-receiver is preset to indicate a fire or fault when the beam's strength is below a certain value.
Your search "" did not match any documents or products.
Reflective Beam Detector (50m Range) | MBD50R |
Reflective Beam Detector (100m Range) | MBD100R |
Mounting Bracket | MRBFP |
Standards: | EN54 Pt12 |
Operating Voltage: | 18Vdc to 30Vdc |
Quiescent Current: | <5mA (no LEDs illuminated) |
Alarm Current: | <9mA |
Alignment Current: | <18mA |
Power up Time: | 20 seconds (approx.) |
Operating Range: | 5 to 50 metres (MBD50R) 5 to 100 metres (MBD100R) |
Fire Alarm Thresholds: | 2.50dB (25%) 3.74dB (35%) 6.02dB (50%) |
Optical Wavelength: | 880nm |
Operating Temperature: | -10°C to +55°C |
Humidity (Non-condensing): | 0 to 93% RH |
Construction: | PC / ABS |
Colour: | White |
Dimensions (HxWxD): | 210mm x 130mm x 120mm |
Weight: | 0.8kg |
Ingress Protection: | IP40 |
Suitable for use with: | Eaton Conventional Fire Systems |