This product has been discontinued and is no longer available. For technical support contact FireTechSupport@Eaton.com.
The Menvier MF9300 is a range of high specification conventional control panels designed for a wide range of building types and sizes.
Available in a choice of 2, 4, 8 or 16 zone versions, the MF9300 range is designed for ease of installation and simple operation.
All panels can be either surface or flush mounted, without the need of additional bezels or back boxes. System flexibility is emphasised by the availability of matching repeater panels for the 4, 8 and 16 zone panels.
Conventional 2 zone control panel | MF9302 |
Conventional 4 zone control panel | MF9304 |
Conventional 8 zone control panel | MF9308 |
Conventional 16 zone control panel | MF9316 |
Conventional 8 zone control panel (24 hour standby) | MF9308L |
Conventional 16 zone control panel (24 hour standby) | MF9316L |
Conventional 8 zone repeater panel | MFR9308 |
Conventional 16 zone repeater panel | MFR9316 |
Code |
MF9302 |
MF9304 |
MF9308 |
MF9316 |
Description |
2 zone control panel |
4 zone control panel |
8 zone control panel |
16 zone control panel |
Standards |
EN54 Pt2 & Pt4 1998 |
EN54 Pt2 & Pt4 1998 |
EN54 Pt2 & Pt4 1998 |
EN54 Pt2 & Pt4 1998 |
Specification |
|
|
|
|
Number of Zones |
2 |
4 |
8 |
16 |
Detectors per Zone |
32 |
32 |
32 |
32 |
Number of Alarm Circuits |
2 |
2 |
4 |
4 |
Alarm Circuit Load |
500mA per circuit. 1A total |
500mA per circuit. 1A total |
500mA per circuit. 2A total |
500mA per circuit. 2A total |
End of Line Devices |
Detection circuits: 12KΩ⏐resistor |
Detection circuits: 12KΩ resistor |
Detection circuits: 12KΩ⏐resistor |
Detection circuits: 12KΩ⏐resistor |
Auxiliary Fire Signal Output |
1A 24V dc (resistive) single pole |
1A 2 4V dc (resistive) single pole |
1A 24V dc (resistive) single pole |
1A 24V dc (resistive) single pole |
Auxiliary Fault Output |
N/A |
1A 2 4V dc (resistive) single pole |
1A 24V dc (resistive) single pole |
1A 24V dc (resistive) single pole |
Auxiliary Common Output |
24V dc pull to 0V. Max 10mA |
24V dc pull to 0V. Max 10mA |
24V dc pull to 0V. Max 10mA |
24V dc pull to 0V. Max 10mA |
Auxiliary dc Output |
24V dc fused. 100mA |
24V dc fused. 100mA |
24V dc fused. 350mA |
24V dc fused. 350mA |
Repeater output |
N/A |
2 wire serial link |
2 wire serial link |
2 wire serial link |
Mains Input Voltage |
230V ac ±10%. 50/60Hz |
230V ac ±10%. 50/60Hz |
230V ac ±10%. 50/60Hz |
230V ac ±10%. 50/60Hz |
System Operating Voltage |
24V dc |
24V dc |
24V dc |
24V dc |
Standby Duration |
72 hours |
72 hours |
72 hours (24 hours option) |
72 hours (24 hours option) |
Battery |
2 x 7Ah sealed lead acid battery |
2 x 7Ah sealed lead acid battery |
2 x 12Ah sealed lead acid battery |
2 x 12Ah sealed lead acid battery |
Recharge Period |
24 hours |
24 hours |
24 hours |
24 hours |
Environmental |
|
|
|
|
Operating Temperature |
-5°C to +40°C |
-5°C to +40°C |
-5°C to +40°C |
-5°C to +40°C |
Humidity (Non Condensing) |
0 to 75% RH |
0 to 75% RH |
0 to 75% RH |
0 to 75% RH |
Physical |
|
|
|
|
Construction |
ABS/Polycarbonate housing & back box |
ABS/Polycarbonate housing & back box |
ABS/Polycarbonate housing & steel back box |
ABS/Polycarbonate housing & steel back box |
Dimensions (H x W x D) |
344mm x 395mm x 95mm |
344mm x 395mm x 114mm |
386mm x 395mm x 114mm |
386mm x 395mm x 114mm |
Weight |
10.6kg |
10.6kg |
16.8kg (24 hours option 16.0kg) |
16.9kg (24 hours option 16.0kg) |
Ingress Protection |
IP20 |
IP20 |
IP20 |
IP20 |
Cable entries |
Top: 13 x 20mm knockouts |
Top: 13 x 20mm knockouts |
Top: 27 x 20mm knockouts |
Top: 27 x 20mm knockouts |
Support from Eaton
Need urgent product technical support?
Phone: +44 (0) 1753 608 700, option 3 then option 4