FRCdM Type B, Bfq and B+ xEffect Residual Current Circuit Breaker

This FRCdM fulfills the highest requirements for the protection of both people and equipment. The RCCB Types B, B+ and Bfq detect AC pulsating DC residual currents and smooth DC residual currents.

The RCCB Type B is the standard type and sensitive to all residual currents up to 1 kHZ. Type B+ is also sensitive to all residual currents and is additionally equipped with a tripping curve thatlimits the tripping current to max. 420 mA for frequencies up to 20 kHz. Whereas the Type Bfq will tolerate systems caused earth leakage currents at higher frequencies up to 50 kHz.

Tripping current
all current sensitive
Compliant to
IEC 61008, IEC 62423
Frequencies
mixed frequencies up to 50 kHz

Viktiga egenskaper

  • Part of the xEffect industrial/commercial series
  • Safe power disconnection at smooth DC and AC
  • Highest system availability by digital technology
  • Real-time measurement of the residual current
  • Easy operation and refitting
  • For fault current/residual current protection and additional protection
  • All-current sensitive RCCB for fault or additional protection
  • Digital features to increase the system availability
  • System monitoring: Preventive information/warning before the RCD trips in case of leakage currents
    – Integrated auxiliary contact for remote prewarning
    – Local Indication through 3 LEDs
  • B+ types also meet the requirements of superior fire-protection systems according to VDE 0664-400
  • 4-pole types can also be used as 2-pole devices for photovoltaic applications
  • New level of accuracy -> reduced unwanted tripping
  • Comprehensive range of accessories
  • Real contact position indicator
  • Fault current tripping indicator
  • Automatic re-setting possible
  • Transparent designation plate
  • Twin-purpose terminal (lift/open-mouthed) above and below
  • Busbar positioning optionally above or below
  • Free terminal space despite installed busbar
  • Universal tripping signal switch, also suitable for FAZ, FRBmM-1N can be mounted subsequently
  • Auxiliary switch Z-HK can be mounted subsequently
  • Contact position indicator red - green
  • Tripping indicator white - blue
  • Additional safety
    - Possibility to seal
    - Possibility to lock in ON and OFF position
  • Delayed types (G, S) suitable for use with standard fluorescent lamps, with or without electronic ballast (30mA-RCD: 30 units per phase conductor)

xEffect Digital Switchgear

The digital RCCB from the xEffect series do more than just switch off. They monitor electrical installations and give advance warning of critical current flows. So plant / factory shutdowns – and the resulting costs – can be avoided.

 

Functioning LED monitoring:

  • The green LED becomes active
    at 0-30% IΔn 
  • Tolerance: ± 5%
  • If the current flow in the system to ground is in the ambit from 0 to 30 % of the nominal fault current, the green LED indicates the proper status.
xEffect Residual Current Circuit Breaker FRCdM Type AC, A, U, R - yellow LED
  • The yellow LED becomes active
    at 30-50% IΔn 
  • Tolerance: ± 5%
  • The yellow LED shows a residual current in the ambit of 30 to 50 % of the nominal fault current. Before the system is shut down, professional countermeasures can be taken.
  • The red LED becomes active
    at >50% IΔn 
  • Tolerance: ± 5%
  • When the red LED lights up, the leakage current is already higher than 50 % of the nominal fault current. Therefore the system is in a critical status – the digital RCCB only trips when the fault current continues to increase.

Type B increases safety and reliability

Smooth DC residual currents can occur in industrial, commercial and residential applications which contain photovoltaic systems, frequency converters or electronic components. The extended sensitivity of the RCCB Type B increases safety and reliability considerably by reducing nuisance tripping.

Reliable protection for machines

These products provide an optimal system and additional protection against residual earth leakage currents for a wide range of applications by offering different tripping characteristics to cater for various electrical systems and components that can generate. Available in a comprehensive range of nominal current values and with optional accessories.

Benefits:

  • Reliable protection for machines with
    3-phase frequency converters
  • Safe power disconnection at smooth DC
    and AC residual Currents
  • Detection of high frequency
    residual currents
  • Highest system availability by
    digital technology and pre-warnings

Digital technology allows permanent indication

The special adapted tripping curve incorporated in the RCCB Type Bfq complies with the specifications of the standard RCCB Type B and avoids in addition unwanted tripping in industrial applications which contains high-power frequency converter controls. Bfq types are the special B type with adapted tripping curve up to 50 kHz for all types of residual current. They are resistant to tripping by leaking currents in circuits with powerful frequency inverters.

Different types offer several advantages

Type -G/B and G/B+: High reliability against unwanted tripping. Compulsory for any circuit where personal injury or damage to property may occur in case of unwanted tripping. Protection against all types of fault currents.
Type -S/B and S/B+: Selective residual current device. Protection against all types of fault currents.
Type -S/Bfq: Suitable for speed-controlled drives with frequency converters inhousehold, trade, and industry.Unwanted tripping is avoided thanks to a tripping characteristic designed particularly for frequency converters. Protection against all types of fault currents.