The DCM2000-21RX is a High Capacity (Low Ohmic) DC Distribution Module (HCLOD) which provides circuit protection for your wide selection of telecommunications loads up 250A per circuit and 1,200A per distribution (600A + 600A) at 60V.
Voltage range | 43 – 60Vdc |
Maximum Current |
1,200A, (600A + 600A |
CB Type |
Heinemann AM1R or AM1P |
CB Current Ratings (Other ratings available upon request - indent) |
Single Position: 15A, 30A, 60A, 80A, 100A Multi Position: 125A(2P), 160A(2P), 175A(2P), 200A(2P), 250A(3P) |
Load Cable Termination |
Two hole lug, vertical cable entry Paralleling bus bar options for 2 & 3 (pole width) breaker sizes. |
Alarms |
MCB Auxiliary contacts, NO.NC switchable on/off |
Operating Temperature Range |
-10 o C to +45 o C (CE) |
Dimensions H,W,D |
4U: 178mm, 480mm (19” mounting), 290mm |
Certifications | CE |