The UL listed Eaton DV2-3G Metro Power Solutions are ideal for low to medium power telecommunications applications requiring compact, efficient and flexible DC power. Typical applications include standby DC power for customer premises equipment, outdoor shelters, VoIP, PABX, data networks and IP routers. 48Vdc systems up to 600A maximum load current. 24Vdc systems up to 500A maximum load current
Input | ||||
AC Supply Voltage* | ||||
North America: | 3P 208Vac nominal | 2P 240Vac nominal | ||
Global: | 3P + N 230/400Vac nominal | 1P + N 230Vac nominal | ||
AC Input Frequency | 50/60 Hz | |||
System | ||||
Rectifier Module* | ||||
APR24-3G | APR48-3G | APR48-ES | ||
Nominal Output Voltage | 24Vdc | 48Vdc | 48Vdc | |
Output Voltage range | 20–30Vdc | 40–58Vdc | 40–58Vdc | |
Max Number of Rectifiers | 10 | 20 | 20 | |
Maximum DC Power† | 14.4kW | 36kW | 40kW | |
Maximum Load Current | 500A | 600A | 600A | |
Efficiency | >91% | >92% | >96% | |
† Maximum DC power includes load and battery recharge. | ||||
Supervisory Module | SC200 | |||
Communications | 10 baseT Ethernet port, web server, SNMP agent | |||
Batteries | Type: Front access VRLA 48V: Up to 600Ahr per cabinet using four strings of 150Ahr batteries. 24V: Up to 1200Ahr per cabinet using eight strings of 150Ahr batteries | |||
Extension Battery Cabinets | Up to six extension battery cabinets fitted with either four strings of 48V or eight strings of 24V in each cabinet | |||
DC Distribution | ||||
Load circuit Breakers | 20-way total | |||
Single Width Circuit Breakers | Heinemann AMIR Series 5A, 10A, 20A, 30A, 40A, 50A, 70A, 80A, 100A | |||
Dual Width Circuit Breakers | Heinemann AMIP 120A, 150A, 200A | |||
Triple Width Circuit Breakers | Heinemann AMIP 250A | |||
Battery Circuit Breakers | Heinemann AM1P, 200A integrated into battery shelf | |||
Low Volt Disconnect Options | 1 x battery disconnect, 1 x 400A non-priority load (10 positions for non priority, 10 positions for priority). | |||
Mechanical | ||||
Dimensions H,W,D | 2000mm [78.7”], 600mm [23.6”], 600mm [23.6”] | |||
With rear cable duct extension H,W,D | 2000mm [78.7”], 600mm [23.6”], 750mm [29.6”] | |||
Weight | DV2-A20B-xxxx: 900kg [1980lb] typical maximum with 20 rectifier modules and 4 x 48V/150Ah battery strings. | |||
Environmental | ||||
Operating Temperature Range | -25°C [-13°F] to 40°C [104°F]* | |||
Humidity | <95% non-condensing | |||
Altitude | <2000m (6500’). Thermally de-rates above this altitude, to a maximum altitude of 4000m | |||
Certifications | ||||
All products comply with International Standards. Contact your local Eaton Power Quality representative for details on the specific product versions available with these safety and EMC approvals: | ||||
North America: | UL Listed 1801, cUL, FCC |