Download document () of 20
Discontinued
Switchboards

Pow-R-Line I Compartmentalized distribution switchboard

Eaton's Pow-R-Line I switchboards provide a compartmentalized design for electrical distribution systems with utility metering, metering, Power Defense molded case circuit breakers, insulated case circuit breakers, surge protection and other various Eaton components. Additionally, it’s designed to meet UL 891 standards for data center, industrial, and healthcare facilities.

Maximum voltage class
600 Vac/Vdc
Interrupting rating
Up to 200 kAIC
Continuous current rating
Up to 4000 A

Core features

  • Available in NEMA 1 and Type 3R enclosures 
  • Offers aluminium or copper bus options
  • Provides service entrance capability
  • Creates a barrier for increased safety as each device is mounted in its own compartment and section
  • Contains both horizontal and vertical buses in bus bar section for installation flexibility
  • Increases safety as rear cable compartment is completely isolated from the bus bars 
  • Eliminates the possibility of accidental contact with the main buses during installation or maintenance with insulated copper runback design

NRX breaker and PXR trip unit technology

Switchboard with compact, innovative and flexible circuit breaker integration

Basics in low-voltage distribution equipment

Gain insight into the definitions, components, applications and other details associated with low-voltage distribution equipment

Customized solutions, customized service

Regional satellite locations provide manufacturing of local, custom, and quick-ship panelboards and switchboards

Get to know more about the Guardian of the grid

Learn more about the Pow-R-Line Xpert family designed to help

giveyou accurate, actionable data to improve efficiency.

More about the Pow-R-Line Xpert family

You may also be interested in

Specifications

Ratings

RATED MAXIMUM VOLTAGE 600 Vac 
CONTINUOUS CURRENT 400-4000 A 
INTERRUPTING RATING 65, 85, 100 and 200 kAIC

Standards

THIRD PARTY APPROVAL/RECOGNITION UL891/cUL (standards)
NEMA PB-2
SEISMIC QUALIFICATION Pow-R-Line distribution switchboard certificate

Devices

PROTECTION DEVICES Molded Case Circuit Breakers, Fusible Switches
METERS Power Xpert MeterIQ Meters
SURGE PROTECTION DEVICES SPD series
DEVICE MOUNTING Fixed and Drawout Mounting

Enclosure

ACCESS Front & rear access only
ENCLOSURE TYPE NEMA Type 1 and 3R
STANDARD INDOOR WIDTH DIMENSIONS 20, 30, 36, 45, 51 inches
STANDARD INDOOR DEPTH DIMENSION 30, 36, 48, 66 inches
STANDARD INDOOR HEIGHT DIMENSIONS 90 inches
CUSTOM DIMENSIONS AVAILABLE Contact satellite manufacturing facility