Eaton’s metal-enclosed breaker (MEB) switchgear consists of a single high-drawout vacuum circuit breaker (Type VCP-W) in a metal-enclosed cabinet.
When deployed as primary protection for a single-ended substation, the MEB can eliminate the need for a secondary main circuit breaker. It can also be applied as the primary main device and integrated with fused or unfused feeder switches in Eaton metal-enclosed switchgear. The MEB 5/15kV switchgear meets or exceeds all required industry standards (IEEE, ANSI and NEMA).
Explore the benefits of Eaton’s MR2, an arc flash safety solution for MV switchgear auxiliaries and circuit breakers.
The Metal Enclosed Breaker (MEB) can be applied in a variety of configurations:
RATED MAXIMUM VOLTAGE | 4.76 kV, 15 kV | |
CONTINUOUS CURRENT | 600 A to 2000 A | |
INTERRUPT RATING | Up to 63 kA rms symmetrical | |
BASIC IMPULSE LEVEL (BIL) | 4.76 kV class - 60 kV peak, 15 kV class - 95kV peak |
ANSI/IEEE STANDARD | C37.20.3, C37.20.4, C37.22, C37.57, C37.58 | |
NEMA | SG-5, SG-6 | |
CSA | C22.2 No. 31-04 | |
THIRD PARTY APPROVAL/RECOGNITION | UL, CSA available for most ratings | |
SEISMIC QUALIFICATION | IBC, CBC |
ACCESS | Front & rear options | |
INSULATING MEDIUM | Air | |
BUS INSULATION | Optional | |
BUS SUPPORTS | Glass Polyester | |
ENCLOSURE TYPE | Indoor & outdoor |
|
INDOOR SECTION DIMENSIONS (TYPICAL) | 36" w x 80" d x 90.38" h |
SWITCHING DEVICE | Vacuum circuit breaker | |
DEVICE MOUNTING | Draw-out |
WEIGHTS | 1600 lbs | |
Your search "" did not match any documents or products.