Eaton's Cooper Power series 6H and V6H three-phase, hydraulically controlled reclosers provide reliable, self-contained distribution-circuit overcurrent protection. Additionally, they’re offered at low cost and require minimal service.
Recloser | 6H | V6H | |
Nominal operating voltage (kV) | 2.4—14.4 |
2.4—14.4 |
|
Maximum continuous current (amps) |
100 | 200 | |
Maximum design voltage (kV) | 15.5 | 15.5 | |
Max interrupting current (symmetrical amps) |
@ 2.4—4.8 kV |
3000 | 3000 |
@ 4.8—8.32 kV |
2500 | 2500 | |
@ 8.32—14.4 kV |
2000 | 2000 | |
Impulse withstand (BIL), 1.2x50 sec wave (crest kv) | 110 | 110 | |
60-Hz withstand (rms kV) |
Dry, one minute | 50 | 50 |
Wet, ten minutes | 45 | 45 | |
Reclosing time (sec) | 1-1/2 | 1-1/2 | |
Bushing creepage distance (in.) | 10-7/8 | 10-7/8 | |
Available trip coils - Continuous current rated (amps) | 5, 10, 15, 25, 35, 50, 70, 100 | 5, 10, 15, 25, 35, 50, 70, 100, 140, 200 |
Recloser | % Interrupting rating | Maximum circuit X/R ratio | Number unit operations | Total unit operations |
6H | 15-20 |
2 | 32 | 68 |
45-55 |
5 | 24 | ||
90-100 |
10 | 12 | ||
V6H | 15-20 |
2 | 128 | 272 |
45-55 |
5 | 96 | ||
90-100 |
10 | 48 |