Eaton's Cooper Power series D and DV hydraulically controlled automatic circuit reclosers provide reliable, economical overcurrent protection for distribution systems. Additionally, the reclosers use oil as the arc-interrupting medium and provide single-phase load protection, tripping and automatic clearing of temporary faults.
Recloser | D | DV | |
Nominal voltage (kv) |
2.4-14.4 |
24.9-34.5 |
|
Maximum design voltage (kv) |
15.5 | 38 | |
Impulse withstand (BIL), 1.2 x 50 microsecond wave, crest (kv) |
110 | 150 | |
60-hz, withstand (kv rms) |
Dry, one minute | 50 | 70 |
Wet, ten seconds | 45 | 60 | |
Maximum continuous current (amps) |
560 | 560 | |
Reclosing time (seconds) |
2 | 2 | |
Bushing creepage distance (inches) |
11-5/8 | 17 |
Trip coil ratings continuous amps |
Minimum trip ratings (amps) |
Interrupting Ratings (rms symmetrical apps) |
|||
Type D |
Type DV |
||||
@4.8 kv |
@8.32 kv |
@14.4 kv |
@24.9, 34.5kv |
||
100 | 200 | 6000 | 6000 | 6000 | 6000 |
140 | 280 | 8400 | 8400 | 8400 | 8000 |
160 | 320 | 9600 | 9600 | 9600 | 8000 |
185 | 370 | 11100 | 10000 | 10000 | 8000 |
225 | 450 | 12000 | 10000 |
10000 |
8000 |
280 | 560 | 12000 |
10000 |
10000 |
8000 |
400 | 800 | 12000 |
10000 |
10000 |
8000 |
400x | 560 | 12000 |
10000 |
10000 |
8000 |
560 | 1120 | 12000 |
10000 |
10000 |
8000 |
560x | 750 | 12000 |
10000 |
10000 |
8000 |