Reclosers

D, DV single-phase reclosers

Eaton's Cooper Power series D and DV hydraulically controlled automatic circuit reclosers provide reliable, economical overcurrent protection for distribution systems. Additionally, the reclosers use oil as the arc-interrupting medium and provide single-phase load protection, tripping and automatic clearing of temporary faults.

High interrupting rating
Cost-effective solution
Hydraulic control
Lower operation and installation costs
Multiple series-trip coils
Simplify system coordination

Core features

  • Sectionalizes single-phase branches of three-phase feeders
  • Offers high, continuous current and interrupting capacity used on heavily loaded circuits with high-available fault currents
  • Provides single-phase load protection, tripping and automatic clearing of temporary faults
  • Features a compact and self-contained operation design
  • Coordinates with circuit breakers, sectionalizers, fuses and other reclosers in the distribution system
  • Supplies the energy for contact closing and stores energy in the trip mechanism with its closing solenoid
  • Uses oil as the arc-interrupting medium

Ready for use on heavily loaded circuits

Eaton's Cooper Power series D and DV reclosers sectionalize single-phase branches of three-phase feeders. The high continuous current and interrupting capacity of the D and DV reclosers enables them to be used on heavily loaded circuits with high available fault currents.

High-voltage solenoid recloser closing

Tripping is initiated by a series-trip coil that releases the stored-energy trip mechanism when an overcurrent occurs. Current-carrying and interrupting capacities depend on the current rating of the series trip coil. A closing solenoid supplies the energy for contact closing and also stores energy in the trip mechanism.
Specifications

Standards

Eaton's Cooper Power series reclosers are designed and tested in accordance with the following ANSI standards: C37.60 and C37.85 and ANSI Guide C37.61

Ratings

Recloser D DV
Nominal voltage (kv)
2.4-14.4
24.9-34.5
Maximum design voltage (kv)
15.5 38
Impulse withstand (BIL), 1.2 x 50 microsecond wave, crest (kv)
110 150
60-hz, withstand (kv rms)
Dry, one minute 50 70
Wet, ten seconds 45 60
Maximum continuous current (amps)
560 560
Reclosing time (seconds)
2 2
Bushing creepage distance (inches)
11-5/8 17

Minimum trip and interrupting ratings

Trip coil ratings continuous amps
Minimum trip ratings (amps)
Interrupting Ratings (rms symmetrical apps)
Type D
Type DV 
@4.8 kv
@8.32 kv
@14.4 kv
@24.9, 34.5kv
100 200 6000 6000 6000 6000
140 280 8400 8400 8400 8000
160 320 9600 9600 9600 8000
185 370 11100 10000 10000 8000
225 450 12000 10000
10000
8000
280 560 12000
10000
10000
8000
400 800 12000
10000
10000
8000
400x 560 12000
10000
10000
8000
560 1120 12000
10000
10000
8000
560x 750 12000
10000
10000
8000

Optional accessories

  • Multi-ratio bushing-current transformers for field installation 600:5 for metering
    • Slip-on bushing current transformer kit
  • Mounting equipment
    • Pole-mounting cluster-type frame for three-type reclosers
  • Phase-to-ground neutral closing coil operating voltage +/-15% (kV)
    • 2.4
    • 4.16-4.8
    • 7.2-7.62
    • 8.0-8.32
    • 14.4
    • 20.0
  • Low-voltage closing coils (Vdc) [Type DV recloser only]
    • 125
    • 250