Eaton's Cooper Power series RVAC pad-mounted vacuum switchgear is designed for applications where frequent 600 A main line switching plus fuse protection is required. It utilizes a vacuum switch mechanism designed specifically for repetitive switching duty. Vacuum switches offer the further advantages of long life in repetitive service, low maintenance and high switching ratings.
15 kV | 25 kV | 35 kV | |
Maximum design voltage |
15.5 | 27 | 38 |
BIL |
95 | 125 | 150 |
1-minute withstand switch* and terminators |
35 | 60 | 70 |
Continuous current, amps |
600 | 600 | 600 |
Load switching, amps |
600 | 600 | 600 |
Momentary current 10 cycles, amps (asym.) |
20,000 | 20,000 |
20,000 |
1 sec., amps (sym.) |
12,500 | 12,500 |
12,500 |
Fault making (sym./asym.), kA |
12.5/20.0 | 12.5/20.0 |
12.5/20.0 |
Interrupting rating**, (kA) |
50 | 20-50 | 12.5-50 |
* The withstand rating of the switch is higher than that of the connectors (IEEE Std C37.74™-2003 standard) |
|||
** Interrupting rating for fused units depends on the selected fuses and the application voltage |
For non-fused RVAC switchgear, the UL listing and labeling is available for units where required with the following features considered to be UL listed and labeled: