Eaton's SP2 is a compact surge protective device with a 45KA per phase footprint and one-inch molded nipple that makes this device easy to install on point of use locations, control panels, load centers and small distribution panels (up to 200amp). With a 10KA nominal discharge rating (ln), low VPR ratings and a 200KA SCCR rating, Eaton's SP2 series surge protective device are ideal for type 1 and 2 applications where dependable performance is required.
Light commercial and UL 508A panels
2 years
Single-phase
Split-phase
Three-phase delta
Three-phase WYE
120
208
240
480
600
two-, three-, four-wire
Matched to nominal voltage
Surges and transients
200 kA
10 kA
45 kA
<25 ns
50/60 Hz
One bi-color LED
(green: good, red: replace)
10 AWG stranded copper/ 18 inches
Chase nipple/bracket
NEMA 4X
UL 94-5VA
IP20
(finger-safe)
Indoor/Outdoor
Lineside/Loadside
UL 1449 3rd edition
Type 1 listed SPD
cULus
RoHS compliant
-40°C to 65°C
(-40°F to 149°F)
12,000 ft
700 L-N
1200 L-N
700 L-N
120 L-L
1200 L-G
2500 L-L
1800 L-G
3000 L-L
700 L-G
1200 L-L
1200 L-G
2500 L-L
1500 L-G
2500 L-L
120
150
Single-phase, two wire
2
240
320
Single-phase, two wire
2
120/240
150
Split-phase, three-wire
3
240
320
Three-phase delta, thire-wire + ground
4
480
550
Three-phase delta, thire-wire + ground
4
120/208
150
Three-phase WYE, three-wire + ground
4
277/470
320
Three-phase WYE, three-wire + ground
4
347/600
420
Three-phase WYE, three-wire + ground
4