Eaton E-series protective relays:

Troubleshooting operation of the device

View all of Eaton's protective relays

Troubleshooting operation of the device

Problem or maloperation in…

Problem description

Corrective action

Relay outputs or LEDs are in unexpected state. A relay output or an LED has been reconfigured from latched to unlatched. Now you need to acknowledge the status once, if it was already pending before the reconfiguration.

Acknowledge the LEDs and relay outputs.

A trip shall be acknowledged without a password.

  Set the password for <Password Level 0> to "empty input". Now you do not have to enter any password for changes and acknowledges on security level 0.
What is the default password?   The factory-provided default password for all security levels is "1234".
How do I reset the password?   Refer to the chapter "forgotten password" of the user manual.

Go back to the main troubleshooting protective relays page.

 