xSolAir is Eaton’s high-performance plug-and-play packaging solution for solar power plant. The medium voltage switchgear, liquid immersed transformers and low voltage assemblies are all in one enclosure. The substation is completely pre-assembled, saving the customer valuable time. On site only the cables need to be plugged in, all the rest is already in place. xSolAir is using a standard seaworthy ISO container, making delivery and logistics much easier.
Adjustable
For 24 kV networks | For 36 kV networks | |||
Tier 1 | Tier 2 | Tier 1 | Tier 2 | |
Product type | Indoor/outdoor, hermetically sealed liquid immersed transformer | |||
Rated power | 2500 kVA | |||
Rated voltages | 20 kV /0,8 kV / 0,8 kV | 30 kV /0,8 kV / 0,8 kV | ||
Tap changer type | Off-Load | |||
# Of taps | 5 | |||
Tapping range | +2x%2,5 / -2x%2,5 | |||
# Of phases | 3 | |||
Frequency | 50 Hz | |||
Connection group | Dyn11yn11 | |||
Insulation class | Class A | |||
High voltage insulation level (Um/AC/LI) | 24 kV / 50 kV / 125 kV | 36 kV / 70 kV / 170 kV | ||
Low voltage insulation level (Um/AC/LI) | 1,1 kV / 3 kV / - | 1,1 kV / 3 kV / - | ||
Altitude | 1000 m | |||
Max. Ambient temp | 40 °C | |||
Temp. Rise (winding) | 65 K | |||
Temp. Rise (oil) | 60 K | |||
Short circuit withstand duration | 2 sec |
For 24 kV networks | For 36 kV networks | |||
Tier 1 | Tier 2 | Tier 1 | Tier 2 | |
Manufacturing standard | IEC 60076-1 | |||
No-load losses | 2012.50 Watt | 1811.25 Watt | 2012.50 Wat t | 1811.25 Watt |
Load losses (@75°C) | 24200.00 Watt | 20350.00 Watt | 24200.00 Watt | 20350.00 Watt |
Total losses (@75°C) | 26212.50 Wat t | 22161.30 Watt | 26212.50 Wat t | 22161.30 Watt |
Uk (@75°C) | 6.00% | 6.00% | 6.00% | 6.00% |
Peak efficiency index | 99.44% | 99.51% | 99.44% | 99.51% |
For 24 kV networks | For 36 kV networks | |||
Tier 1 | Tier 2 | Tier 1 | Tier 2 | |
Cooling method | ONAN | |||
Cooling structure | Corrugated Wall | |||
Liquid type | Mineral Oil | |||
High voltage / low voltage winding material | Aluminum | |||
Core steel type | Cold Rolled Grain Oriented | |||
Tank cover | Bolted | |||
Corrosion category | C2 | |||
Paint | RAL 7033 | |||
High voltage bushing | 24 kV 250 A / Porcelain / On top | 36 kV 250 A / Porcelain / On top | ||
Low voltage bushing | 1 kV 1250 A / Porcelain / On top | 1 kV 1250 A / Porcelain / On top |
For 24 kV networks | For 36 kV networks | |||
Tier 1 | Tier 2 | Tier 1 | Tier 2 | |
Width | 1130 mm | 1110 mm | 1150 mm | 1190 mm |
Lenght | 1830 mm | 1850 mm | 1830 mm | 1930 mm |
Height | 2280 mm | 2310 mm | 2450 mm | 2490 mm |
Total weight | 5080 kg | 5430 kg | 5420 kg | 5910 kg |
Switchboard type | Xiria family switchboard | Uring family switchboard |
Insulation | Air | SF6 |
Rated voltage | 24 kV | 36 kV |
Service voltage | 20 kV | 30 kV |
Main busbar current rating | 630 | 630 A |
Frequency | 50 Hz | 50 Hz |
Short circuit whitstand | 20 kA/3 sec | 16 kA/3 sec - 20 kA/1 sec |
Average ambient temp | 40 | 40 |
Internal arc | 20 kA/1 sec | 16 kA/1 sec |
Power frequency withstand | 50 kA | 70 kV-80 kV |
Lightning impulse withstand | 125 k A | 170 kV-195 kV |
Protection degree | IP3X | Shell:IP3X / SF6 Tank:IP67 |
Switchboard type | xEnergy Main |
Rated voltage | 800 V |
Service voltage | 800 V |
Frequency | 50 Hz |
Configuration standard | IEC 61439-2 |
Average ambient temp | 35 °C |
Main busbar current rating | 2000 A |
Rated short circuit current | 25 kA |
Main busbar system | 4P + PE |
Bus bar dimentions (phases) | 3x30x10 mm |
Bus bar dimentions (neutral) | 3x30x10 mm |
Bus bar dimentions (earth) | 1x80x10 mm |
Height | 2000 mm |
Width | 1000 mm |
Depth | 1200 mm |
Weight | 540 kg |